background image

Mode Number
(Press   

  key

Factory-Setting

Other Choices  

(Press 

 or  

▼ 

key to change)

Select

to change)

Display

Description

Display

Description

Not used

01

Fan operation

02

01

Heat pump and electric
heat applications where
thermostat controls fan
operation in heat mode.

00

Conventional applications where
equipment controls fan operation
in heat mode.

Not used

03

Heating cycle
rate

04

03

3 cph used for
conventional systems

01, 06,  
or 09

01—1 cph used for radiant floor
heat, gravity systems
06—6 cph used for conventional
systems.
09—9 cph used for electric heat
systems

Not used

05 thru 11

Changeover
(T8501D only)

12  

00

Automatic changeover

01

Manual changeover

Not used

13  

Degree  
temperature
display

14

00

Temperature is
displayed in °F

01

Temperature is displayed in °C

Not used

15 thru 18  

Extended fan
operation in
heating

a

19  

01

Fan operation is
extended 90 seconds
after the call for heat
ends.

00

No extended fan operation after
the call for heat ends

Extended fan
operation in
cooling

20  

01

Fan operation is
extended 90 seconds
after the call for cool
ends

00

No extended fan operation after
the call for cool ends

Not used

21 thru 23  

Outdoor
temperature
display

24

00

No outdoor temperature
is displayed

01

Outdoor temperature is displayed.
Needs a C7089B1000 Outdoor
Sensor to operate.

a Mode 02 must be set to 01 to extend fan operation.

69-1312-1

INSTALLATION INSTRUCTIONS

®U.S. Registered Trademark

ATA11H01

Microelectronic Thermostat

T8501D1087

Use form 69-0959 except use Table 2  and the hookup diagrams that follow.

Table 2. Thermostat installer setup options.