A C D U 0 3   C o m m u n i c a t i n g   S e r v i c e   To o l

R e v. :     N o v e m b e r   3 ,   2 0 1 7

ClimateMaster’s Communicating Service Tool (ACDU03) allows install and service technicians to confi gure and diagnose 
ClimateMaster Digital Communicating Units without installing a digital communicating thermostat.  

Using the Service Tool, a technician can ELECTRONICALLY:

1. Confi gure items like: airfl ow, heat pump options and confi guration, pump or modulating valve operation, unit family, unit 

size, etc.

 AND

2.  Diagnose the unit by operating it manually, performing control diagnostics, viewing dip switch confi gurations, or by 

viewing fault history and operating conditions when a fault occurred.

The Service Tool connects to the DXM2 board with a 4-Wire Connector as shown below:

P1

Alarm

O

Y1

Y2

W

G

C

R

AL1

R

C

R

NSB

AL2

JW1

P2

P5

B-

Gnd

A+

24V

Service tool

connection

DXM2

Board

DXM2

DXM2

Board

Board

1.0  Connection

 

WARNING! 

WARNING! Connecting wire harness while unit is 
powered on or connecting backward may damage 
service tool.

Note: For Vertical Stack models (TSM, TSL) must 
order harness for connection to service port outside 
chassis. Harness part number 11B0100N27. DXM2 to 
service port is factory wired.

Содержание ACDU03

Страница 1: ...orking properly and or may void the warranty on both the thermostat and the equipment Section Title Page 1 0 Connection 3 2 0 Menu Structure 4 3 0 System Configuration 4 3 1 Airflow Selection 4 3 2 Option Selection 5 3 3 Unit Configuration 5 3 4 Pump Configuration 6 3 5 Valve Configuration 6 3 6 Multi Unit Configuration 7 4 0 Service Mode 8 4 1 Manual Operation 8 4 2 Control Diagnostics 8 4 3 Dips...

Страница 2: ...This page was intentionally left blank ...

Страница 3: ...nit by operating it manually performing control diagnostics viewing dip switch configurations or by viewing fault history and operating conditions when a fault occurred The Service Tool connects to the DXM2 board with a 4 Wire Connector as shown below P1 Alarm O Y1 Y2 W G C R AL1 R C R NSB AL2 JW1 P2 P5 B Gnd A 24V Service tool connection DXM2 Board DXM2 DXM2 Board Board 1 0 Connection WARNING WAR...

Страница 4: ...tem has no blower Note 2 The Pump Configuration menu section 3 4 will not be present if the connected communicating control is configured for No Loop Configuration OTHER Note 3 The Valve Configuration menu section 3 5 will not be present if the connected communicating control is configured for No Loop Configuration OTHER 3 1 AIRFLOW SELECTION Adjust the airflow settings for each system operating m...

Страница 5: ...efore restarting NOTE 2 If multiple units are connected to one thermostat refer to section 3 6 for unit selection 3 3 UNIT CONFIGURATION Adjust the Unit Configuration settings including Heat Pump Family Heat Pump Size Blower Type and Loop Configuration using the up down arrow buttons Press the center button to select each item Heat Pump Family default stored in control valid range TE TY TES TEP TR...

Страница 6: ...ol press use down arrow to select Fixed and press to save Default stored in control Valid range 15 90 in 1 increments Heating Stage 1 Cooling Stage 1 Heating Stage 2 Cooling Stage 2 If Pump Configuration is set to VS PUMP PARALLEL valid range changes to 50 90 in 1 increments 3 5 VALVE CONFIGURATION Configure temperature differentials at the thermostat for vFlow units with a motorized modulating va...

Страница 7: ... to the ATC thermostat or connected to one another in series as shown by the figure below 3 6 1 MULTI UNIT AIRFLOW SELECTION In section 3 1 when an installer selects Airflow Selection from the System Configuration menu the installer may choose the unit to configure by the last 4 digits of its serial number from the following screen 3 6 2 MULTI UNIT OPTION SELECTION In section 3 2 when an installer...

Страница 8: ... pump at the thermostat Navigate between diagnostic screens using the left right arrow buttons NOTE The Pump Status will not be present if the connected communicating control DXM2 is not configured for Pump section 3 4 SERVICE MODE MANUAL OPERATION CONTROL DIAGNOSTICS DIPSWITCH CONFIG FAULT HISTORY CLEAR FAULT HISTORY SELECT OPTION PREVIOUS SELECT MANUAL OPERATING MODE Y1 COMM OUTPUT OFF Y2 COMM O...

Страница 9: ...TSTAT 4 ON RV O THERMOSTAT 5 ON DEHUMID OFF 6 ON EH2 AUX HEAT 7 ON BOILERLESS 8 ON SEE DXM2 AOM PREVIOUS NEXT CONTROL CONFIGURATION DIPSWITCH S2 1 ON ACCESSORY 1 2 ON ACCESSORY 2 3 ON 4 ON ACCESSORY 2 5 ON ACTIVE W COMP 6 ON 7 ON H DEHUM INPUT 8 ON FACTORY SETTING PREVIOUS NEXT CONTROL CONFIGURATION DIPSWITCH S3 1 ON FACTORY SETTING 2 OFF HWG TEST OFF 3 OFF HWG SP 125 4 OFF HWG DISABLED JW3 LT1 SE...

Страница 10: ...TIONS FAULT I O CONDITIONS FAULT CONFIG COND FAULT POSSIBLE CAUSES PREVIOUS SELECT FAULT TEMPERATURE CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 LT1 TEMP 28 1 LT2 TEMP 97 3 HOT WATER EWT 121 5 COMP DISCHARGE 157 7 LEAVING AIR 92 7 LEAVING WATER 34 9 ENTERING WATER 42 1 CONTROL VOLTAGE 26 4 PREVIOUS FAULT I O CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 TSTAT SAFETY OUTPT CONV COMM H...

Страница 11: ...ult History will clear all fault codes stored in the thermostat as well as the fault history in any connected communicating controls DXM2 AXM FAULT CONFG CONDITIONS LT1 LOW WATER TEMP HEAT 1 11 11 AM 11 14 S1 S2 S3 1 ON 1 ON 1 ON 2 ON 2 ON 2 OFF 3 ON 3 ON 3 OFF 4 ON 4 ON 4 OFF 5 ON 5 ON 6 ON 6 ON LT1 WELL 7 ON 7 ON LT2 WELL 8 ON 8 ON PREVIOUS POSSIBLE FAULT CAUSES LOW WATER COIL TEMP LOW WATER TEM...

Страница 12: ...ined herein are not express warran ties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products ClimateMaster Inc 2012 97B0106N01 7300 S W 44th Street Oklahoma City OK 73179 Phone 405 745 6000 Fax 405 745 6058 climatemaster com Rev Janua ry 2 3 2 0 1 9 Date Page Description 23 Jan 19 3 4 Update harness and service tool par...

Отзывы: