Hot Water Generator Module Refrigeration Installation
Outdoor Compressor Section Only
Figure 16a: Outdoor Compressor Section HWG Installation
Fully Insulated
Lines to the HWG
Refr to
HWG
Refr from
HWG
Table 8: HWG Refrigerant Line Sizing
Figure 16c: HWG Service Valves
Figure 16d: HWG Bypass Valve
Figure 17: HWG Wiring
Valve Open
(HWG Bypassed)
Valve Closed
(HWG Activated)
Control
Board
Circulator
HWG
Water Out
HWG
Refr Out
HWG
Refr In
High Voltage
HWG
Water In
Figure 16b: Remote HWG Module
Capacity
Line Set Size
1/2” OD
5/8” OD
3/4” OD
2 Ton
Up to 16 ft.
[4.9m]
Up to 30 ft.
[9.1m]
N/A
3 Ton
Up to 9 ft.
[2.7m]
Up to 25 ft.
[7.6m]
Up to 30 ft.
[9.1m]
4 Ton
Up to 5 ft.
[1.5m]
Up to 13 ft.
[4.0m]
Up to 30 ft.
[9.1m]
5 Ton
N/A
Up to 9 ft.
[2.7m]
Up to 25 ft.
[7.6m]
E
E
E
HWG
Line Valves
HWG
Bypass
Valve
Refr
to HWG
Refr from
HWG
R e s i d e n t i a l S p l i t U n i t s - 6 0 H z P u r o n
®
R e v. : 6 D e c . , 2 0 1 1
30