Figure 4, R560 configuration in PA Pro II
The configuration of each input type can be done in the PA Pro II. The correct type needs to be
entered to ensure correct values with applicable scale and offset.
Table 3, input types for configuration in PA Pro II
Input type Description
10
PT1000 with an offset of 0.35 K
20
Voltage, 0-10 V
21
5 Bar pressure transducer with 0-5V output
22
10 Bar pressure transducer with 0-5V output
23
35 Bar pressure transducer with 0-5V output
24
50 Bar pressure transducer with 0-5V output
25
150 Bar pressure transducer with 0-5V output
30
Resistance, 0-
1600 Ω
40
Current, 4-20 mA (check section 2.2)
41
0-25 mm/s Vibration sensor with 4-20mA output
50
Resistance, 0-
5000 Ω