R560 Hardware Manual
–
2021-01-13 Page 6 of 9
2.2
Change Analog input mode
DIP switches for the analog inputs can be found in between the AI terminals on the bottom side of
the device, see Figure 1. Default setting is 0-10V and PT1000 (DIP switch 1-8
OFF
). In this mode
each input is configured on the ClimaCheck Online server or in the PA Pro III configurator, see PA
Pro III Hardware manual for details. For current measurement (0-20mA) the particular DIP switch
is changed to ON, see Table 2 and Figure 3.
Table 2, Input mode Dip switch, all set to 0-10V
Figure 3, Analog input DIP switch, AI_5 set to current measurement
2.3
Configuration on PA Pro II
It is possible to use the R560 with PA Pro II. To configure, the R560 script needs to be uploaded to
the PA Pro. Contact ClimaCheck support for more information. With the script in place, follow the
steps below:
-
Connect the PA Pro to your computer
-
Open a web browser and enter
http://169.254.1.1
-
The default user name is
“config”
and password
“ef56”
(default)
-
Select
Settings
->
Advanced
- >
External Units
-
Select a unit
-
Ensure the correct type of unit is selected
R560
-
Check
Activate
and click
OK
.
-
Select the same unit again
-
Enter the
address
and the
type
for each input. Check Table 3 for more information. Input
type 10 is selected in the example of Figure 4.
-
Select the telegram update times: 1 minute (or longer) for
Set input type
and 10 seconds
for
Read all
-
Click
OK
-
Continue the setup process by connecting the external channels and activating them