Hardware Manual 

 

 

Analog input module - R560 

 

 

 

2021-01-13 

 

 

Содержание R560

Страница 1: ...n AB Box 46 SE 131 06 Nacka Sweden Visiting address Gamla Värmdövägen 6 SE 131 37 Nacka Sweden Tel 46 0 8 50 255 250 Email info climacheck com Web www climacheck com Hardware Manual Analog input module R560 2021 01 13 ...

Страница 2: ...e of Contents 1 Technical data 3 1 1 Power supply 3 1 2 Analog inputs 3 2 Configuration 4 2 1 Change Modbus address 4 2 2 Change Analog input mode 6 2 3 Configuration on PA Pro II 6 3 ClimaCheck Onsite portable version 8 4 Electrical wiring diagram 9 ...

Страница 3: ...560 unit is supplied with 24V DC via the serial communication cable connected to the panel In ClimaCheck online installations the R560 unit is supplied with 24 VDC from the common power supply but it can handle 10 35 V DC 1 2 Analog inputs There are 8 analog inputs on the unit configurable for temperature sensors Pt1000 pressure transducers or other sensors with voltage 0 10V current 4 20mA or res...

Страница 4: ...s to PT1000 or to configure additional R560 modules See the PA Pro III hardware manual for more details 2 1 Change Modbus address Modbus address is set with DIP switches marked ADR on the top left side of the unit see Figure 1 Address is entered as binary where DIP8 bit 0 switches increase their bit weight from right to left Default address for module 1 is 00010100 20 module 2 is 00010101 21 and s...

Страница 5: ...R560 Hardware Manual 2021 01 13 Page 5 of 9 Table 1 Modbus address dip switch ...

Страница 6: ...ro II It is possible to use the R560 with PA Pro II To configure the R560 script needs to be uploaded to the PA Pro Contact ClimaCheck support for more information With the script in place follow the steps below Connect the PA Pro to your computer Open a web browser and enter http 169 254 1 1 The default user name is config and password ef56 default Select Settings Advanced External Units Select a...

Страница 7: ... configuration in PA Pro II Input type Description 10 PT1000 with an offset of 0 35 K 20 Voltage 0 10 V 21 5 Bar pressure transducer with 0 5V output 22 10 Bar pressure transducer with 0 5V output 23 35 Bar pressure transducer with 0 5V output 24 50 Bar pressure transducer with 0 5V output 25 150 Bar pressure transducer with 0 5V output 30 Resistance 0 1600 Ω 40 Current 4 20 mA check section 2 2 4...

Страница 8: ... 8 are connected to tele plug inputs and inputs 1 2 5 and 6 have both a tele plug and a DIN 5D each to be able to handle both types of sensors see electrical wiring diagram and Table 4 Note that it is not possible to use an input for both PT1000 and pressure transducer Table 4 AI Available connection 1 Tele plug and DIN 5D 2 Tele plug and DIN 5D 3 Tele plug 4 Tele plug 5 Tele plug and DIN 5D 6 Tel...

Страница 9: ...R560 Hardware Manual 2021 01 13 Page 9 of 9 4 Electrical wiring diagram ...