1942500
V2.0
30 September 2022
Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Zoneworks, HIVE and DATA Monitored Options
Fittings with part numbers -ZW
, -HV/-HVG, -DATA
are fitted with Zoneworks communications modules
(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also
be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a
single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides
a multifunction indication of the status of the fitting during testing and normal operation:
Option
State
LED Operation
ZW, HV, HVG
DATA
Commissioned
LED on Solid (Green)
ZW, DATA
Un-commissioned
Batt plugged-in:
yellow 1s, green 1s
Batt unplugged:
red 1s, off 1s
HV, HVG
Un-commissioned
With network connectivity
Batt plugged-in:
yellow 1s, green 1s
Batt unplugged:
red 1s, off 1s
HV, HVG
Un-commissioned
Without network connectivity
Batt plugged-in:
yellow 250mS, green
250mS, yellow 250mS, green 250mS,
green 1s
Batt unplugged:
red 250mS, off
250mS, red 250mS,off 250mS, off 1s
ZW, DATA
Emergency Light Test In Progress
LED flashes at yellow 5s , 0ff 1s
HV, HVG
Emergency Light Test In Progress
LED flashes at yellow 1s , 0ff 1s
In the case of the DATA version a 2-
way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EMERGENCY Option
Luminaires with part numbers having
-DALI
are fitted with DALI modules (nodes) that facilitate connection
and integration to 3
rd
Party Lighting Control Systems. Before installing the -DALI luminaire, please confirm
that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI
fitting will be addressed and configured into the control system by the Lighting Control System
Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Lamp and Status LED Flash for 30 seconds
Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours after disconnection
from the mains supply.
•
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are
required to be recorded in a service logbook, which is to be always kept on-site. If the unit fails to
remain illuminated for the requisite time, remedial action must be taken to repair the situation and
once completed, the unit must pass a subsequent test. For more specific information, please refer to
the current edition of the AS/NZS 2293.2 and AS/NZS 60598.2.22 Standards.
LP™ Weatherproof Jumbo LED Exit
One Box Solution
Installation & Maintenance Instruction Leaflet
Victoria (Head Office &
Manufacturing)
Website:
Email:
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
New South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9207 0000
Fax:
+61 8 9207 0088
New Zealand
Phone:
+64 800 548 448
Dimensions: 570mm x 117mm x 340mm Weight 5.6KG
Designed in Australia to comply with the requirements of
AS/NZS 2293.3: 2018 and AS CISPR15: 2017
NOTE: Standard product codes with this symbol are enabled
with Clevertest Plus capability. Please refer to the operation
guide supplied with the product for details.
Models:
CJWELED-40-xx-yy-uu-ww
Testing:
Options:
Manual Test
xx = Blank
Tamperproof
yy=TP
Zoneworks
xx = ZW
Uninterrupted Power Supply ww=UPS
Z/W DATA
xx = DATA
Black Colour
uu=BLK
Zoneworks HIVE
xx = HV/HVG
DALI Registered.
xx = DALI
Spare Parts:
1550030
Replacement Battery
AUM02370110001
Replacement Emergency Driver
8050640
Replacement Emergency LED Board
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction.
As a result, any Exit & Emergency Units, on these circuits, will have their batteries discharged or “cycled”. The
Li-ion battery in this fitting has been selected to give excellent long-life performance in a controlled AS 60598.2.22
testing environment. Excessive battery cycling will reduce through-life performance and may lead to premature
battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics
warranty terms.