Installation:

 

The Jumbo LED Exit can be Wall or Ceiling Mounted:  

Wall Mounting -WM

 (single sided) 

 

Remove one of the corner trim pieces 

 

Remove the back-mounting plate. 

 

Determine power entry  

 

Position the mounting plate in the mounting position.  

 

Mark the 4 holes for mounting. Then install the appropriate fixings (not supplied). 

 

Reinstall the mounting plate to the fitting. 

 

Install the fitting on the mounting hardware, while routing the power cable through the access hole. 

 

Ensure connection of the grounding strap between the fitting and the back plate. 

 

Connect the 240VAC supply to the terminal block. 

 
Ceiling Mounting -CM

 (single or double sided) 

 

Remove one of the corner trim panels. 

 

Determine power entry 

 

Position the fitting in the mounting position. 

 

Mark the mounting holes at the top of the fitting. 

 

Then install the appropriate fixings (not supplied). 

 

Position the fitting while routing the power cable and attach to the surface as required. 

 

Connect the 240VAC supply to the terminal block. 
 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 
Segment Marking on the p

roduct will include an ‘’F’’ in third segment block. 

 
Networking: 

When installing the product on a monitored network, (ZONEWORKS, HIVE, DATA, DALI) simply insert 
the relevant Smart Node PCA. 

Dimensions: 

 

Wall Mounting Plate 

 

Ceiling Mounting Plate 

 
 
 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 
Battery Replacement: 

1. 

Prior to any work, isolate the power to the luminaire that requires battery replacement 

2. 

Open the fitting by removing one of the corner trim pieces. 

3. 

Slide out protective cover, decal and diffuser.  

4. 

Remove the Battery Connector from the Emergency Driver. 

5. 

Remove the battery from the gear tray by removing mounting screws.  

6. 

Replace battery, re-install screws and connecter to Emergency Driver. 

7. 

Reinsert protective cover, decal, diffuser, and replace the corner trim piece. 
 

Lamp Replacement:

 

 

Use only the LED lamp strip recommended on the label inside the Exit fitting or this instruction. 
 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 
Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage.

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

 