This CBS2N Surface mount non-maintained Emergency Luminaire can be installed on solid surface or 
used to replace an existing unit. 

 

Locate the installation position. 

 

Refer Images and Dimensions below for the Cut-out Hole and other dimensions. 

 

Pre-drill mounting holes 

 

Mount base plate and use suitable fixings to secure the base plate into the pilot holes 

 

Bring in supply cables via the rear entry hole or via the end of the base plate (surface mount 
conduit entry) 

 

Terminate the supply cables to the L, N & E terminals (in the case of the 

–DALI or –DATA fittings 

terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Install the top cover, containing the control gear, ensuring to reconnect the control gear assembly 
to the connector from the supply terminal block   

 

Ensure the Battery is connected 

 

Screw the cover to the base plate and, in the case of side/conduit entry remove the knock-out at 
the end of the cover to go cover the conduit 

 

If the CTP capabilities are activated, please affix the CTP Status Label to a visible surface.

 

 
Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 
relevant Smart Node PCA. 
 

Images and Dimensions:

 

 

 

 
 
 
 

Initial Testing:

 

 
When the CBS2N unit is connected to the un-switched active, it must be allowed to charge the battery 
for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct the following 
tests: 
 

 

During the first commissioning test the emergency lamp must illuminate for at least 2 hours after 
disconnection from the main supply. The results of all tests are required to be recorded in a service 
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time, 
remedial action must be taken to repair the situation and once completed, the unit must pass a 
subsequent test.  

 

 

Press and hold Test Button for each LED head or switch Off Mains Supply, check that the 
emergency lamps are On. 

 

 

Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-
maintained operation). 

 

Below are a list of common problems and their possible causes: 

 

Fault:  

The Green LED indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected. 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer 
to spacing tables for installation positions):

 

 

 

C0=D40  C90=D40 
 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any fittings, on these circuits, will have their batte

ries discharged or “cycled”. 

The Li-ion battery in the fitting has been selected to give excellent long life performance in a controlled 
IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life performance and 
may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically 
EXCLUDED from Clevertronics warranty terms. 
 