background image

GENERAL

This  luminaire  is  used  in  places  with  low 

o

t e m p e r a t u r e   ( - 2 0 C )   w h e r e   e m e r g e n c y  
luminaires are needed.
Each  illumination  sign  must  be  permanently 
connected  to  mains  power  supply

.

  In  normal 

operation  the  led  strip  lights  and  the  battery  is 
charging.

 

In  case of  a  mains  power  supply 

failure    the  illumination  sign  will  light  the  led 
strip  automatically in emergency mode. When 
the  mains  power  supply  is  restored  the  device 
turns to normal operation.

INSTALLATION

To  install  the  luminaire  follow  the  installation 
instructions on page 3.

Battery Charging

The  battery  charging  is  completely  controlled

In  this  case,  is

 

achieved  the  perfect  battery 

maintenance

as  well  as  the  elongation  of  its 

duration

When  the  battery  has  completely 

charged

it  charges  with  a  maintenance 

current.

Battery Cut-off

The luminaire enters in this operation when the 
mains  power  supply  fails

 

and  battery  has  lost 

its 

energy

During 

this 

operation 

the 

illumination  sign  enters  the  idle  state

 

and 

battery consumption is negligible, in order to be 
protected from deep discharge.

Manual

 Test

The  manual  test  can  be  conducted  only  if  the 
mains  power  supply  and  the  battery  is 
connected.  By  pressing  the  TEST/RESET 
button  briefly  (page  3)  an  emergency  operation 
test  is  initiated.  During  this  test  period  all 
indication LEDs are OFF. 

Automatic Operational Test

This test includes all the operations that provide 
the  manual  test  and  is  conducted  automatically 
every  15  days.  In  order  to  be  performed,  the 
mains  power  supply  and  the  battery  should  be 
connected.

Manual Autonomous Test

If  the  Test  button  is  pressed  for  a  period 
between 5 to 10 seconds (with the battery  fully 
charged),  the  illumination  sign  will  enter  in 
counting  autonomy  condition. 

If  the  battery  is 

not  fully  charged  this  command  is  ignored

. The 

BATTERY 

FAULT 

blinks 

during 

the 

measurement,  indicating  this  process  to  the 
user.  This  measurement  duration  is  equal  with 
the  nominal  autonomous  duration  of  the 
illumination sign (1.5 hour or 3 hours) and at the 
end  of  the  process,  if  the  measured  duration 
was  at  least  the  nominal  autonomous  duration, 
the BATTERY FAULT is turned OFF, in the other 
hand  stays  continuously  ON  indicating  to  the 

Page

 1

 from

 5

92

3

9390

16

_09_00

7

WATERPROOF SELF TESTING MAINTAINED EMERGENCY LUMINAIRES

ΤΕΧΝΙΚΑ ΧΑΡΑΚΤΗΡΙΣΤΙΚΑ

90 min

Charge, Lamp fault, Battery fault 

TEST button

EN 60598-1, EN 60598-2-22

, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

31W / 33

VA 

(

<0°C

)

3

.

6

V / 2Ah

GR-938/30L/LT

180 min

24h

From overcharge and deep discharge

4 years

IP

65

  

2

80lm 

/

 

2

3

0

lm 

  White LEDs

o

-20 to 

+

40  C

Up to 95% 

Bayblend FR3010

transparent

 

polycarbonate

3 years 

(1 

year for the battery

)

940gr.

1050gr.

32W / 

3

5

VA 

(

<0°C

)

3

.

6

V / 4Ah

220-240VAC

 

50-60Hz

363 x 145 x 73 mm

GR-93

9

/30L/LT

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT

GUARANTEE 

OPERATION VOLTAGE

MAXIMUM POWER CONSUMPTION

CHARGING TIME

INDICATIONS 

CONTROLS

BATTERY PROTECTION

EXPECTED BATTERY LIFETIME

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

ILLUMINATION (MAINS / EMERGENCY)

ILLUMINATION SOURCE 

BATTERIES (Ni-ΜΗ)

TECHNICAL CHARACTERISTICS

 

(for LED MODULE Specifications see page 4)

Thank you for your trust in our products.  

Olympia Electronics -  European manufacturer

.

Отзывы: