Page
4 from
5
92
3
9390
16
_09_00
7
Status of LEDs
Led status explanation
GREEN
YELLOW
RED
Normal
Charging
Battery duration test (auto or manual)
Battery fault
Battery fault and light source fault
Charger and battery fault (or mains off and battery fault)
Charger and light source fault (or mains off and light source fault)
Charger, battery and light source fault (or mains off, battery and light source fault)
1Hz: Heating circuit fault
5Hz: Open circuit of heating resistors
Light source test
Light source fault
Steady ON
Steady OFF
Flashing in 1Hz or 5Hz
Charger fault, battery not connected
or mains off
LEDs
Description
The heating circuit faults are:
1) Open circuit of the heat sensor.
2) Short circuit of the heat sensor.
o
3) When the heated area is >50 C. All the above faults are indicated as long as they
exist. When they are restored, they will be erased and not indicated by the indication
LEDs.
LED MODULE CHARACTERISTICS
Olympia Electronics S.A
45 °C max. across the board
Cable connection with non-reversible connectors
14-16.5V DC
5
.
4W
GR-938/30L
/
LT
GR-939/30L/LT
0505175/30L
Manufacturer
Model Number
Voltage Range
Connections
Nominal Power
Temperature (tc)