Clevertronics Clevertest and Clevertest Plus 

 

Refer to the supplementary operation guide supplied with the Product.

 

 

 

After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red 
flashing for a period up to 2 minutes. 

 
Zoneworks and DATA Monitored Options

 

Fittings with part numbers CBS2N-ZW

CBS2N-DATA are fitted with Zoneworks communications modules 

(nodes).These  fittings  are  monitored  using  either  Powerline  Carrier  Technology  that  utilizes  the  power 
cable  to  provide  data  communication  or  a  dedicated  data  cable  to/from  data  routers  installed  on  a 
dedicated data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre). 
Zoneworks software on the server is used to monitor, coordinate testing and collate test data from each 
fitting.  Zoneworks  fittings  can  be commissioned  by  a  single  push  of the test  switch,  or scanning  of  the 
supplied barcode. The LED Test Switch indicator provides a multifunction indication of the status of the 
Lifelight during testing and normal operation: 

State

 

LED Operation

 

Commissioned 

LED on Solid (Green) 

Un-commissioned 

LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow) 

Emergency Light Test In Progress 

LED flashes at 3s On (Yellow) & 0.5s Off 

 
In the case of the DATA version a 2-

way “figure 8” cable and terminal block facilitates the connection to 

the DATA network via a multi-drop bus (daisy chain connection).  For further information of installation of 
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA 
version)  
 

DALI EM Option

 

Fittings  with  part  numbers  CBS2N-DALI  are  fitted  with  DALI modules  (nodes)  that facilitate  connection 
and integration to 3

rd

 Party Lighting Control Systems.  Before installing the CBS2N -DALI please confirm 

that the Lighting Control System has the capability to monitor DALI Emergency Luminaires.  The CBS2N 
-DALI  will  be  addressed  and  configured  into  the  control  system  by  the  Lighting  Control  System 
Commissioning Technicians and not Clevertronics.   

State

 

LED Operation

 

Commissioned/ Un-commissioned 

LED on Solid (Green) 

Emergency Light Test in progress 

LED flashes at 1s On (Yellow) & 1s Off 

“IDENTIFY COMMAND” 

Fitting goes into emergency mode for 10 seconds 

 
A 2-

way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way 

“structured wiring system” lead and plug facilitating the power and DALI connection.  DALI connections 
are marked as Da Da.  

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

LP

™ LED Non-Maintained Batten  

Surface Mount Emergency Luminaire 

Installation & Maintenance Instruction Leaflet

 

 

Designed in Australia to comply with the 
requirements of AS2293.3: 2005 and AS/NZS 
CISPR15: 2011. 
 

NOTE: Standard product codes with this    
symbol are enabled with Clevertest Plus 
capability.  Please refer to the operation guide 
supplied with the product for details.

 

Victoria (Head Office & Manufacturing) 

195 Chesterville Rd Moorabbin VIC 3189  

Phone:

 +61 3 9559 2700  

Fax:

 +61 3 9559 2799 

 

News South Wales

 

Phone: 

+61 2 8805 6400

 

Fax:    

+61 2 8805 6444 

 

Queensland

  

Phone:

  +61 7  3442 9700 

Fax:

     +61 7  3442 9777 

 

South Australia/Northern Territory

  

Phone:

 +61 8 8301 8800 

Fax:

   +61 8 8351 8286 

 

Western Australia

  

Phone:

 +61 8 9248 3720 

Fax:

   +61 8 9248 3725 

 

New Zealand 

Phone: +64 800 548 448

 

Models:  

 

CBS2N

-xx-yy 

Testing

 

:

 

 

 

Options

:

   

 

 

Manual Test  

xx = Blank 

 

Black Colour 

  yy = BLK 

 

Zoneworks 

xx = ZW 

 

 

 

 

Zoneworks DATA    xx = DATA 

 

 

 

 

DALI Compatible       xx = DALI 

 

 

 

 

Clevertest 

xx = CT 

 (

NOTE: Products supplied with the Clevertest Plus Symbol     are 

activated  with  Clevertest PLUS capability. Please  refer  to  the  operation 

guide supplied with the product for details). 

Spare Parts:  
 

1550010 

Battery, LP 3.2V 3.2Ahr, 200mm Lead Bracket 

1100930 

CLIFE LED Head Assembly - White 

CLIFE-CKIT-NP 

Lifelight, Control Gear Only, LP Lithium 

 

Important:

 

 

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation, 
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in 
accordance with the relevant Australian and International Standards.

 

 

 

 

 

 

 

 

Отзывы: