Installation:

 

The L10 Weatherproof Supalite (LWFLED) is Wall Mounted. The LWFLED is housed in a weatherproof 
enclosure. The enclosure base is attached to the wall using screws installed through the 4 isolated holes. 
Once the base is mounted and wired the gear tray and cover are installed. Please follow the steps below 
to install the Weather Proof Exit: 
 

 

Remove the enclosure cover.  

 

Remove the gear tray. 

 

Determine power entry. 

 

Drill power access hole in the box base. 

 

Position the box base in the mounting position.  

 

Mark the 4 holes for mounting. Install the base using appropriate fixings (not supplied). 

 

Connect the 240VAC supply to the terminal block on the Gear Tray. 

 

Reinstall the gear tray. 

 

Reinstall the enclosure cover. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 
Segment Marking on the p

roduct will include an ‘’F’’ in third segment block. 

 
Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE, DALI) simply insert 
the relevant Smart Node PCA. 

Mounting Hole Dimensions: 
 

 
 
 
 
 
 
 

Testing:

 

When the Supalite unit is connected to the un-switched active, it must be allowed to charge the battery 
for at least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the following 
tests: 
 

 

The emergency lamps must illuminate for at least 2 hours after disconnection from the mains. The 
results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all 
times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the 
situation and once completed, the unit must pass a subsequent test.  

 

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamps are On. 

 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamps are Off 
(Non-maintained operation). 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 
Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 