1942122
V1.4
3 March 2020
Installation:
Note: The fitting is designed to be installed as shown in the image below.
This LWP2LIFE-PRO-WPPOD Surface mount non-maintained Emergency Luminaire can be
installed as either ceiling mount with the PODs facing down or on the wall with the PODs rotated to
face down.
•
When wall mounting the fitting must be mounted 32mm off the wall to allow pods to rotate
•
Locate the installation position.
•
Pre-drill mounting holes per diagram below.
•
Removed fitting cover.
•
Use suitable fixings to fasten the fitting to the mounting surface.
•
Taking note of the terminal block positon, drill a hole in the fitting box to suit the cable gland or
conduit to be used for power entry. Please ensure that the cable entry is appropriately
sealed to maintain the IP65 rating.
•
Terminate the supply cables to the L, N & E terminals (in the case of the –DALI or –DATA
fittings terminate the DALI or DATA cable to the terminals marked Da Da or DATA).
•
Ensure the Batteries and POD cables are connected.
•
To rotate the PODs for the wall mount (WM) position loosen the internal locking nut, rotate
and re-tighten the nut.
•
Screw the cover to the base.
Networking:
When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert
the relevant Smart Node PCA.
Images and Dimensions:
Testing:
When the LWP2PIFE-PRO-WPPOD unit is connected to the un-switched active, it must be allowed to charge
the battery for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct the
following tests:
•
During the first commissioning test the emergency lamp must illuminate for at least 2 hours after
disconnection from the main supply. The results of all tests are required to be recorded in a service
logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time,
remedial action must be taken to repair the situation and once completed, the unit must pass a
subsequent test.
•
Press and hold Test Button in each POD or switch Off Mains Supply, check that the emergency lamp is
On.
•
Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off (Non-
maintained operation).
Below are a list of common problems and their possible causes:
Fault: The Green LED indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected.
Test Switch for damage.
Fault: Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault: Lamp illuminates in emergency mode, but only stays on for a short period.
Check: Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1 (refer to
spacing tables for installation positions):
Refer to the Technical Label for classification.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or “cycled”.
The Li-ion battery in the Lifelight has been selected to give excellent long-life performance in a controlled IEC
60598-2-22 testing environment. Excessive battery cycling will reduce through-life performance and may lead
to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED
from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/
Note: The image below shows the
LWP2LIFE-PRO-WPPOD in the wall
mount configuration with the PODs
rotated down. To mount to the ceiling
using the same mounting instructions
but ensure the heads are facing down.
Note: When
rotating the
PODs in WM
position ensure
the PODs are
level with the
bottom of the
main enclosure.