Installation:
The LLIFE-PRO-SM is a Surface Mount (SM) fitting that can be attached directly to any solid surface (use
appropriate fixings to suit the mounting surface). Please follow the steps below to install the LLIFE- PRO-
SM:
•
Remove the Lid from the Base by using a flat screwdriver to release the snap fits (see below)
•
Cut/Drill out Cable Entry points (see image below)
•
Drill out the required fixing holes on the Base (see image below)
•
Mark holes on mounting surface (use drilled out holes on the Base as a template)
•
Mount Base using appropriate fixings to ensure a secure installation (pre-drill holes if required)
•
Insert Mains Cables through Cable Entry
•
Terminate the Mains Cables into terminal block. Ensure Active, L & Neutral, N wires are connected
as per Terminal Block Label.
•
Re-attach Lid Assembly, ensuring to align Mains Connector Pins into Terminal Block
•
If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four
Segment Marking on the p
roduct will include an ‘’F’’ in third segment block.
Networking:
When installing the product on a monitored network, (HIVE, DALI) simply insert the relevant Smart Node
PCA.
Dimensions:
Lid Removal:
Testing:
Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24
hours. Conduct the following tests:
•
For the first test, the emergency lamp must remain illuminated for at least 2 hours after
disconnection from the mains supply.
•
Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails
to remain illuminated for the requisite time, remedial action must be taken to repair the situation
and once completed, the unit must pass a subsequent test. For more specific information, please
refer to the current edition of the AS 2293.3 Standard.
Trouble Shooting:
Below are a list of common problems and their possible causes.
Fault:
The Green LED Test Switch indicator is not illuminated.
Check: A.C. is connected and is turned on.
Battery is connected
Test Switch for damage.
Fault:
Lamp does not illuminate in emergency mode.
Check: A.C. is connected.
Lamp is correctly inserted.
Battery is connected
Fault:
Lamp illuminates in emergency mode, but only stays on for a short period.
Check:
Battery has been allowed to charge for at least 24 hours.
Battery for damage.
Rated Emergency Lumen Output in accordance with AS2293.1, not applicable
for
–TH (theatre) version (refer to spacing tables for installation positions):
Refer to the Technical Label for classification information.
Caution:
On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such
abuse, are specifically EXCLUDED from Clevertronics warranty terms.
Warranty:
For Product Warranty information and Terms and Conditions of Sales please refer to our website
http://clevertronics.com.au/terms-conditions-sale-australia-nz/