Installation:

 

The LLIFE-PRO-SM is a Surface Mount (SM) fitting that can be attached directly to any solid surface (use 
appropriate fixings to suit the mounting surface). Please follow the steps below to install the LLIFE- PRO-
SM: 

 

Remove the Lid from the Base by using a flat screwdriver to release the snap fits (see below) 

 

Cut/Drill out Cable Entry points (see image below) 

 

Drill out the required fixing holes on the Base (see image below) 

 

Mark holes on mounting surface (use drilled out holes on the Base as a template) 

 

Mount Base using appropriate fixings to ensure a secure installation (pre-drill holes if required) 

 

Insert Mains Cables through Cable Entry 

 

Terminate the Mains Cables into terminal block. Ensure Active, L & Neutral, N wires are connected 
as per Terminal Block Label. 

 

Re-attach Lid Assembly, ensuring to align Mains Connector Pins into Terminal Block 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 
Segment Marking on the p

roduct will include an ‘’F’’ in third segment block. 

 
Networking: 

When installing the product on a monitored network, (HIVE, DALI) simply insert the relevant Smart Node 
PCA. 

Dimensions: 

Lid Removal: 

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 
Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

 

Rated Emergency Lumen Output in accordance with AS2293.1, not applicable 
for 

–TH (theatre) version (refer to spacing tables for installation positions): 

 

 

 

Refer to the Technical Label for classification information.

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 