Installation: 

This Lifelight Pro Cylindrical Surface Mount Emergency Luminaire can be installed on solid or T-BAR 

ceilings or used to replace an existing unit. 

 

Locate the installation position. 

 

Refer Images and Dimensions below for the Cut-out Hole and other dimensions. 

 

Pre-drill mounting holes. 

 

Mount base plate and use suitable fixings to secure the base plate into the pilot holes. 

 

Bring in supply cables via the rear entry hole.  

 

Terminate the supply cables to the L, N & E terminals (in the case of the –DALI or –DATA fittings 

terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Install the cylindrical top cover, containing the control gear, ensuring to reconnect the control gear 

assembly to the connector from the supply terminal block. 

 

Ensure the Battery is connected. 

 

Screw the cover to the base plate. 

 

For HIVE version please install provided antenna on the side. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 

Segment Marking on the product will include an ‘’F’’ in third segment block. 

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, HIVE, DALI) simply insert 

the relevant Smart Node PCA. 

 

 

 

Images and Dimensions: 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Testing:

 

When the Lifelight Pro Cylindrical Surface Mount Emergency Luminaire unit is connected to the un-

switched active, it must be allowed to charge the battery for at least 24 hours. The emergency lamp only 

illuminates during a power fail. Conduct the following tests: 

 

 

The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The 

results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all 

times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the 

situation and once completed, the unit must pass a subsequent test.  

 

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Below are a list of common problems and their possible causes: 

 

Fault:   The Green LED indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected. 

Test Switch for damage. 

 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer 

to spacing tables for installation positions):

 

 

 

Refer to the Technical Label for classification information. 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 

discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 

performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-

life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 

abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

 