
Chapter 5
Adjustment Procedures
5-6
750-364
of its efficiency, because an efficient gas flame will vary from
transparent blue to translucent yellow.
Most flue gas analyzers in use today measure the content, by
percentage of oxygen (O
2
) and carbon monoxide (CO) either
by percent or parts per million (ppm). Carbon dioxide (CO
2
)
is not normally measured with todays flue gas analyzers, but
may be displayed via a calculation.
The O
2
levels through the entire firing range of the burner,
low fire to high fire should be tested. Cleaver-Brooks
recommendations on turndown should also be followed and
the turndown range of the burner should not be exceeded.
It’s important to understand what the readings shown on an
instrument refer to when setting combustion in a boiler. To
assist with this understanding Figure 5-3 shows the
relationship between O
2
levels (excess air) and the products
of combustion for a typical flue gas analysis (natural gas).
One of the products of combustion is CO
2
(Carbon Dioxide).
This is shown in percentage.
Another product of combustion is CO (carbon monoxide) and
is shown in both percentage and parts per million (ppm). The
maximum CO level standardly allowed is less than 400 ppm.
However, this may change subject to local regulations.
The percent O
2
recorded on an instrument equates to percent
excess air, I.E. 3% O
2
is approximately 15% excess air and
4% O
2
is approximately 20% excess air. The exact percentage
of excess air is a mathematical calculation based on an
ultimate fuel analysis of the fuel being fired.
It is generally recommended that O
2
readings of between 3%
to 5% be attained with less than 400 ppm CO, at high fire.
Using information from Section G, determine the standard
conditions of gas pressure and flow for the size boiler and the
gas train on it. Calculate the actual pressure and flow through
the use of correction factors that compensate for incoming
gas pressure and altitude.
Basically, gas adjustments are made with a gas pressure
regulator, which controls the pressure and with the butterfly
gas valve
which directly controls the rate of flow.
The low fire setting should be regarded as tentative until the
proper gas pressure for high fire operation is established.
To reach the high fire rate, manually increase in minor
increments while monitoring combustion for overly rich or
lean conditions.
At high fire, the gas butterfly valve should be open as wide as
indicated by the slot on the end of the shaft.
Determine the actual gas flow from a meter reading. (See
Section G) With the butterfly valve open and with regulated
gas pressure set at the calculated pressure, the actual flow rate
should be close to the required input. If corrections are
necessary, increase or decrease the gas pressure by adjusting
the gas pressure regulator, following the manufacturer's
directions for regulator adjustment.
When proper gas flow is obtained, take a flue gas reading.
The O
2
should be between 3% and 5% at high fire.
If the fuel input is correct, but the O
2
values do not fall within
this range, the air damper settings may need to be adjusted.
With the high-fire air/fuel ratio established, the gas pressure
regulator needs no further adjusting.
After being certain that the air control damper and its linkage
are correctly adjusted to provide the proper amount of
secondary air, and after adjusting the gas pressure regulator,
final adjustment can be made, if necessary obtain a constant
air/fuel ratio throughout the entire firing range.
Input of combustion air is ordinarily fixed at any given point
in the modulating cycle, the flue gas reading is determined by
varying the input of gas fuel at that setting. Standard Burner
Low Fire Adjustment
The fuel input should be adjusted using the linkage to
approximately 33% of that at high fire. At low fire the O
2
flue
gas reading should be between 3-5%.
If the air damper needs to be adjusted in order to provide the
correct low fire air/fuel ratio, combustion must be rechecked
at higher firing rates and adjusted as required.
I. LOW GAS PRESSURE SWITCH
Adjust the scale setting to slightly below the normal burning
pressure. The control circuit will be broken when pressure
falls below this point. Since gas line distribution pressure
may decrease under some conditions, shutdowns may result
if the setting is too close to normal. However, regulations
require that the setting may not be less than 50% of the rated
pressure downstream of the regulator.
Manual resetting is necessary after a pressure drop. Press the
reset lever after pressure is restored.
LGPS
HGPS
J. HIGH GAS PRESSURE SWITCH
Adjust the scale setting to slightly above the normal burning
pressure. The control circuit will be broken when pressure
exceeds the normal operating pressure. Unnecessary
shutdowns may result if the setting is too close to normal;
however, regulations require that the setting may not be
greater than 150% of rated pressure.
Manual resetting is necessary after a pressure rise. Press the
reset lever after pressure returns to normal.
1
2
3
Содержание FLX 1250
Страница 6: ...iv...
Страница 10: ...Chapter 1 GENERAL DESCRIPTION 1 4 750 364...
Страница 32: ...Chapter 3 Pressure Vessel Care 3 10 750 364...
Страница 49: ...Troubleshooting Chapter 6 750 364 6 5...
Страница 50: ...Chapter 6 Troubleshooting 6 6 750 364...
Страница 58: ...Chapter 7 Inspection and Maintenance 7 8 750 364...
Страница 65: ...Parts FLX 750 364 8 7 Temperature Controls 2 2 3354 817 3354...
Страница 66: ...FLX Parts 8 8 750 364 Level Controls...
Страница 69: ......
Страница 70: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...