Condensing Economizers
Part No. 750-266
2-3
The units are shipped in enclosed crates. To remove the economizer, first position the unit, while either
still in the shipping container or on the skid, as close to the installation site as possible. Then attach
a lifting hoist to all the lifting lugs located on the top lid or cone.
The economizer is generally shipped in the position it is designed to be installed in. Depending on size,
some exchangers are shipped on wooden pallets and/or mounted on structural steel skid for fork lift
removal and/or installation. The very large exchangers if installed in the vertical position are shipped
on the side. Use all lifting lugs when lifting. To remove a large exchanger from the flat bed, attach a
lifting hoist to all the lifting lugs as required when lifting from horizontal to the vertical position. For
the extremely large heat exchangers be sure to have an experienced crane operator(s) for removal from
the flat bed and positioning. If there are any questions during the removal and installation of the
exchanger please do not hesitate to contact your authorized Cleaver-Brooks representative for
suggestions. All exchangers include steel pads for mounting to the final support (supplied by others)
as required by the installation.
NOTE:
Spare parts may be shipped within the crate or skid mounted unit. Spare parts shipped within
the unit will be located beneath the damper bypass assembly in a separate shipping box.
To avoid delays in moving the economizer into position, have a fork lift and scaffolding ready prior to
receipt of the unit.
2.3-INSTALLATION
Consult submittal data for specific weights and dimensions to ensure a well designed and safe
installation when either hanging or supporting the exchanger.
The exchanger is shipped ready to be mounted in the vertical or horizontal position as originally
specified (consult the factory if a change in the gas flow direction is desired).
For existing retrofit installations, ensure that the combustion source has been turned off and has
cooled.
In some installations a spool piece may be required between the boiler and the economizer to prevent
interference with the davit arm. On some boilers it may also be required due to panels mounted on
the front of the boiler.
A condensate drain connection is provided at the base of the unit. Header manifold inlet/outlet
connections are provided for makeup water and feedwater.
Содержание C1X Series
Страница 1: ...Economizers 750 266 1 15 CRE CCE C2X C1X Operation Manual...
Страница 2: ......
Страница 6: ...vi NOTES...
Страница 20: ...Standard Economizers 1 14 Part No 750 266 Figure 1 7 Piping with circulating tank BOILER...
Страница 29: ...Condensing Economizers Part No 750 266 2 9 Figure 2 7 Dimension diagram C2X BB...
Страница 33: ...Condensing Economizers Part No 750 266 2 13 Figure 2 9 Single boiler with deaerator...
Страница 34: ...Condensing Economizers 2 14 Part No 750 266 NOTES to Figure 2 9 CONTACT LOCAL CB REPRESENTATIVE IZING...
Страница 36: ...Condensing Economizers 2 16 Part No 750 266 Figure 2 10 Single boiler with deaerator and surge tank...
Страница 38: ...Condensing Economizers 2 18 Part No 750 266 2 4 3 Two boilers with deaerator refer to Figure 2 11...
Страница 39: ...Condensing Economizers Part No 750 266 2 19 Figure 2 11 Two boilers with deaerator...
Страница 40: ...Condensing Economizers 2 20 Part No 750 266 NOTES to Figure 2 11 CONTACT LOCAL CB REPRESENTATIVE IZING...
Страница 42: ...Condensing Economizers 2 22 Part No 750 266 Figure 2 12 Two boilers with deaerator and surge tank...
Страница 51: ...Condensing Economizers Part No 750 266 2 31...
Страница 52: ...e mail info cleaverbrooks com Web Address http www cleaverbrooks com...