2
1. General Information
1.1 Introduction
This instruction manual describes the CLAUDGEN
Surface Warm Air Ceiling Heaters.
The heater is designed to be suspended from the
ceiling.
1.2 General
All installations must be in accordance with the
regulations in force in the country of use.
These instructions must be handed to the user on
completion of the installation.
Installers and service engineers must be able to
demonstrate competence and be suitably
qualified in accordance with the regulations in
force in the country of use.
To ensure continued and safe operation it is
recommended that the appliance is serviced
annually.
The heater outlet / inlet must not be obstructed
during use.
1.3
Electrical Supply
Electrical supply is 230/240V single phase,
Neutral and Earth. The maximum cable inlet size is
4mm².
It is recommended that the electrical supply to the
base unit in the heater is via an appropriate
switched isolator in accordance with the
regulations in force in the country of use and must
be via a fused isolator having a contact separation
of greater than 3mm on all poles.
BMS control, time switches, room thermostats and
door interlocks can be installed at the discretion
and responsibility of the installer.
All units must be wired in accordance with I.E.E
regulations for the Electrical Equipment of
Buildings and the installer should ensure that a
suitable isolating switch is connected in the mains
supply.
1.4 Controller `SL` models
The HE7237SL, HE7247SL, HE7267SL heaters are
supplied without a controller. The `SL` models will
not work without the controller. See section 5.1 for
more details.
1.5 Controller `RX` models
The HE7237RX, HE7247RX, HE7267RX heaters are
supplied without a controller. The `RX` models will
not work without the controller. See section 5.2 for
more details.
1.6 Location
All units should be installed horizontally. It is
recommended that the ceiling heater is
suspended using four 10mm rods.
Care must be taken to allow complete free air
movement into the inlet grilles of the unit to
ensure the correct working operation of the
heater. If the HE7237SL/RX or HE7247SL/RX heaters
are mounted close to the wall or corner the
discharge opening should be facing the wall. The
minimum distance from the wall or corner is 0.8m
or 1.2m for the HE7267SL/RX.
1.7 Clearance distances
It is acceptable for the heater to sit flush to the
ceiling.
The minimum mounting height (floor to grille) is
2.2m for the HE7237SL/RX, HE7247SL/RX and 2.5m
for the HE7267SL/RX.
The recommended mounting height is 2.5m for
the HE7237SL/RX, HE7247SL,RX and 3m for the
HE7267SL/RX.
CONSORT SL Controllers
41001476 Iss 01
SLPB
SLTI
SLVT
CONSORT Wireless
controller CRX2
SLVTB
Содержание HE7237SL
Страница 7: ...7 ...