1. General Information 

1.1  Introduction 

This  instruction  manual  describes  the  commer-

cial fan heater range from Consort. These heat-

ers  are  robustly  designed  for  use  in  large  open 

areas. With a maximum heat throw of up to 11m, 

they  are  ideal  for  areas  such  as  garages,     

workshops and warehouses.  

Each  heater  is  equipped  with  an  intelligent  fan     

control,  which  allows  the  heater  to  adapt  to  the 

environment  by  automatically  adjusting  the  fan 

speed.  The  heater  provides  instant  directional 

warmth,  and  also  has  a  fan-only  setting  for  air 

circulation.  

The heaters are wall mounted with               multi

-directional  brackets,  and  can  be  operated  by  a 

remote switch. 

1.2  General

 

All  appliances  must  be  installed  in  accordance 

with  the  regulations  enforced  in  the  country  of 

use. 

These  instructions  must  be  handed  to  the  user 

on completion of the installation. 

Installers and service engineers must be able to 

demonstrate  competence  and  be  suitably     

qualified in accordance with the regulations. 

To  ensure  continued  and  safe  operation,  it  is   

recommended  that  the  appliance  is  serviced       

annually. 
The  commercial  fan  heater  slots  must  not  be   

obstructed during use. 

 

1.3  Electrical Supply 

The  unit  must  be  wired  in  accordance  with  IEE 

regulations  for  the  Electrical  Equipment  of    

Buildings,  and  the  installer  should  ensure  that  a 

suitable  isolating  switch  is  connected  in  the 

mains supply. 

Electrical supply for the CH06CSi model is 240V 

single phase, neutral and earth.  

Electrical supply for the CH06CPi and CH09i/12i 

models  is  either  240V  single  phase,  or  415V 

three phase, neutral and earth.  

Electrical  supply  for  the  CH15i  model  is  415V 

three phase, neutral and earth.  

BMS  control,  time  switches,  room  thermostats 

and  door  interlocks  can  be  installed  at  the      

discretion and responsibility of the installer. 

1.4   Controller 

All  commercial  fan  heaters  are  controlled  via  a  

remote switch that can provide three levels of heat. 

The  remote  switch  also  includes  a  fan  boost    

function. 

 

 

 

 

 

 

The  remote  control  unit  houses  4  single  pole  10A 

switches.  The  heater  can  also  be  controlled      

remotely  via  BMS  or  any  controls  with  a  contact 

rated at 5A. The controller is wired to the base unit 

via  an  appropriately  sized  cable,  specified  by  the 

current IEE standard. 

 

1.5  Clearance Distances

 

 

It  is  recommended  that  there  is  a  minimum     

clearance of 200mm between the upper surface of 

the heater and the ceiling surface.  
The  unit  should  be  fitted  between  2.5m  and  3m 

from  the  ground  (CH06CSi/CPi)  or  between  2.5m 

and 4m (CH09i/12i/15i). 

The unit should be positioned so that the airflow is 

not  obstructed.  Never  install  heaters  opposite  to 

each other.  
 

1.6  Health and Safety 

 

Sole  liability  rests  with  the  installer  to  ensure  that 

all  site  safety  procedures  are  adhered  to  during 

installation. 
Sole  liability  rests  with  the  installer  to  ensure  that 

protective safety wear such as hand, eye, ear and 

head  protection  is  used  during  installation  of  the 

product.  

Do  not  rest  anything,  especially  ladders,  against 

the product. 

 

1.7  Standards 

Units  conform  to  the  European  electrical  standard 

BS EN 60335-2-30. 

51000214 Iss 01 

Содержание CH06CPi

Страница 1: ...rnton Industrial Estate Milford Haven Pembrokeshire SA73 2RT Tel 01646 692172 Fax 01646 695195 Mon to Thu 8 30am to 4 30pm Fri 8 30am to 3 30pm Email technical consortepl com Web www consortepl com IN...

Страница 2: ...utral and earth Electrical supply for the CH06CPi and CH09i 12i models is either 240V single phase or 415V three phase neutral and earth Electrical supply for the CH15i model is 415V three phase neutr...

Страница 3: ...lso be connected on a 230 240 volt 50Hz supply The maximum current draw for the 06CPi 09i 12i models are 25A 37 5A and 50A for single phase and approximately 8 3A 12 5A and 16 6A per phase for a three...

Страница 4: ...own on Fig 3 Secure the wall bracket to the wall with suitable fix ings Ensure the position of this bracket will allow suitable clearances between the heater when fitted and adjacent walls Minimum of...

Страница 5: ...e rating For controlling up to 2 heaters 3A up to 4 heaters 5A up to 10 heaters 13A For more connection details see figures 5 and 6 for the CH06CSi and CH06CPi CH09i 12i 15i models respectively The wi...

Страница 6: ...of fan failure or an obstruction of the free airflow by two thermal cut outs If this happens the thermal cut outs effectively switch off the appliance The appliance will not operate until the thermal...

Страница 7: ...7 CH06CSi Wiring Diagram 51000214 Iss 01...

Страница 8: ...8 CH06CPi Wiring Diagram 51000214 Iss 01...

Страница 9: ...9 CH09i 12i 15i Wiring Diagram 51000214 Iss 01...

Страница 10: ...10 51000214 Iss 01...

Отзывы: