1. General Information
1.1 Introduction
This instruction manual describes the commer-
cial fan heater range from Consort. These heat-
ers are robustly designed for use in large open
areas. With a maximum heat throw of up to 11m,
they are ideal for areas such as garages,
workshops and warehouses.
Each heater is equipped with an intelligent fan
control, which allows the heater to adapt to the
environment by automatically adjusting the fan
speed. The heater provides instant directional
warmth, and also has a fan-only setting for air
circulation.
The heaters are wall mounted with multi
-directional brackets, and can be operated by a
remote switch.
1.2 General
All appliances must be installed in accordance
with the regulations enforced in the country of
use.
These instructions must be handed to the user
on completion of the installation.
Installers and service engineers must be able to
demonstrate competence and be suitably
qualified in accordance with the regulations.
To ensure continued and safe operation, it is
recommended that the appliance is serviced
annually.
The commercial fan heater slots must not be
obstructed during use.
1.3 Electrical Supply
The unit must be wired in accordance with IEE
regulations for the Electrical Equipment of
Buildings, and the installer should ensure that a
suitable isolating switch is connected in the
mains supply.
Electrical supply for the CH06CSi model is 240V
single phase, neutral and earth.
Electrical supply for the CH06CPi and CH09i/12i
models is either 240V single phase, or 415V
three phase, neutral and earth.
Electrical supply for the CH15i model is 415V
three phase, neutral and earth.
BMS control, time switches, room thermostats
and door interlocks can be installed at the
discretion and responsibility of the installer.
1.4 Controller
All commercial fan heaters are controlled via a
remote switch that can provide three levels of heat.
The remote switch also includes a fan boost
function.
The remote control unit houses 4 single pole 10A
switches. The heater can also be controlled
remotely via BMS or any controls with a contact
rated at 5A. The controller is wired to the base unit
via an appropriately sized cable, specified by the
current IEE standard.
1.5 Clearance Distances
It is recommended that there is a minimum
clearance of 200mm between the upper surface of
the heater and the ceiling surface.
The unit should be fitted between 2.5m and 3m
from the ground (CH06CSi/CPi) or between 2.5m
and 4m (CH09i/12i/15i).
The unit should be positioned so that the airflow is
not obstructed. Never install heaters opposite to
each other.
1.6 Health and Safety
Sole liability rests with the installer to ensure that
all site safety procedures are adhered to during
installation.
Sole liability rests with the installer to ensure that
protective safety wear such as hand, eye, ear and
head protection is used during installation of the
product.
Do not rest anything, especially ladders, against
the product.
1.7 Standards
Units conform to the European electrical standard
BS EN 60335-2-30.