background image

6

Revised 08/09

V SERIES

Cartridge Dust Collector

6. SERVICE

Figure 7. Rear Access

61-10039-0001

Collected dust may be hazardous. Consult proper
authorities for handling and disposal.

4. The filter monitor gauge should read between 

0.1" and 0.5" w.g. while unit is operating with 
clean filters.

5.  The discharge plenum on the V Series collector

can be rotated in 90

Ý

 increments to direct the

discharge air in multiple directions. The discharge
housing will be factory installed with the discharge
pointing towards the floor as shown in Figure 7.

Collecting Particles

1. Locate the unit, arm and hood in the best position

to collect contaminants as generated by the
process or operation, and where operator
interference is minimal.

2. Position the hood to minimize the influence of

cross drafts from outside air sources or other
operations.

3. Position the hood slightly higher than the source,

with the face of the hood approximately 45° from
horizontal. The hood shape is designed for high-
velocity pick up. It should be located as close to
the source as practical and no further than 14-16"
from the contaminant source.

3. Check diaphragm valves to ensure proper pulse

cleaning. With the cleaning cycle activated, the valve
should pulse at approximately 10-second intervals.
Remove lid of control panel enclosure to view the
timer. 

4. Check the filter monitor gauge at start-up. The

cleaning system should be activated when the gauge
has increased 0.5" w.g. above the start-up pressure
drop. Allow unit to pulse clean until the original
reading is achieved or until the gauge reading will
not decrease after six consecutive pulses.

5.2 CHECKLIST

1. Check the clean air outlet. Discharge air should

remain visibly clean. If a leak should develop, it will
be first noticed after a cleaning pulse as a puff of
dust.

2. Check pressure drop on the pressure gauge 

(see Figure 6). Pressure drop across elements is
considered normal between 0.5-5.0" w.g. Pressure
drop will generally read between 1-2" for “seasoned”
filters.

The following procedure requires access to an area of
the unit where high voltage is present. Access should
be restricted to qualified personnel.

Figure 6. Control Panel Layout Detail

61-10039-0002

3. Turn the unit on by pushing the "Power" rocker

switch to the ON position (refer to Figure 6). On 
3-phase units, fan rotation will need to be verified 
by matching fan rotation with the rotation decal on
the blower housing. Rotation should be clockwise 
as viewed from the motor or drive side. Any two
motor starter leads should be reversed if the 
rotation is not correct.

Содержание UAS V Series

Страница 1: ...VERSATILE PORTABLE CARTRIDGE DUST COLLECTOR V SERIES MODELS VB VF VP OWNER S MANUAL Model VB Model VP Model VF ...

Страница 2: ...ailable when contacting UAS UAS ORDER ________________________________________________________________ UNIT MODEL _______________________________________________________________ UNIT SERIAL _______________________________________________________________ FILTER PART ________________________________________________________________ SYSTEM ACCESSORIES __________________________________________________...

Страница 3: ...ion VP Model 3 4 2 2 Downdraft Table Assembly VB Model 4 4 2 3 Fixed Unit Assembly VF Model 4 4 3 Pulse Cleaning 4 4 4 Electrical Installation 4 4 4 1 Pulse Control Timer Board 4 5 OPERATION 5 5 1 Start Up 5 5 2 Checklist 6 6 SERVICE 6 6 1 Filter Removal and Replacement 6 6 2 Dust Drawer Removal 7 6 3 After Filter Removal Installation 7 6 4 Servicing Direct Drive Blower 8 7 ELECTRICAL 8 7 1 Unit C...

Страница 4: ...r to put cigarettes or any burning object into the hood or ducting of the swing arm Do not use the Swing Arm to move the portable air cleaner if applicable DA N G E R WARNING C AU T I O N C A U T I O N This is the safety alert symbol This symbol alerts you to potential hazards that can kill or hurt you and others All safety messages will follow the safety alert symbol and the word DANGER WARNING o...

Страница 5: ... reduces the air stream velocity This provides even distribution of the air stream across the entire surface area of the cartridge filters allowing a uniform dust cake to form The reduced air stream velocity causes the heavier particles to fall out and collect in the dust drawer The air stream then passes through the cartridge filter where it is stripped of the particles by the media Cleaned air f...

Страница 6: ...s inches Width Depth Height 30 1 4 30 1 4 27 7 16 27 7 16 27 7 16 27 7 16 52 3 4 38 13 16 52 3 4 38 13 16 52 3 4 38 13 16 46 13 16 46 13 16 31 3 4 31 3 4 38 7 16 38 7 16 Shipping Weight lbs 440 365 405 335 450 375 Filter Area ft2 283 141 283 141 283 141 SCF Per Pulse 1 3 1 1 1 3 1 1 1 3 1 1 Sound Level dBA 77 5 79 3 81 6 74 4 81 6 74 4 AMCA tested sound levels at 5 feet Horsepowers of V Series uni...

Страница 7: ...er or gasket has not become displaced during shipment refer to Section 6 1 Cartridge Filter Removal and Replacement Replace covers once inspection is complete 4 2 INSTALLATION Different models of the V Series collector require different assembly techniques Please see the techniques in the subsequent sections for your V Series dust collector All models of the V Series will require minimum clearance...

Страница 8: ...4 and 1 diameter The compressed air usage per cleaning cycle can be found in Table 1 Note that the cleaning system will only operate when the motor blower is off See Section 4 4 1 for adjustments available with the timer board 4 4 ELECTRICAL INSTALLATION The V Series unit has a wide variety of available electrical options to best meet your needs Take care to ensure proper installation in whatever ...

Страница 9: ...a cleaning cycle See Figure 5 for Cleaning Control Switch Settings Upon motor blower shutdown downtime cleaning will only be performed if the CLEAN SWITCH is in the ON position before the motor blower is turned OFF During downtime cleaning the CLEAN light will flash for the duration of the cycles selected 5 OPERATION 5 1 START UP 1 Position unit in desired location NOTE Do not attempt to move the ...

Страница 10: ... cleaning cycle activated the valve should pulse at approximately 10 second intervals Remove lid of control panel enclosure to view the timer 4 Check the filter monitor gauge at start up The cleaning system should be activated when the gauge has increased 0 5 w g above the start up pressure drop Allow unit to pulse clean until the original reading is achieved or until the gauge reading will not de...

Страница 11: ...cover gaskets and reinstall cover by tightening the knob securely to the retaining nut until the gasket is adequately compressed Figure 8 Cartridge Filter Removal 61 10039 0003 6 2 DUST DRAWER REMOVAL 1 To access and remove the dust drawer located at the base of the V Series unit you must first unseal the drawer by pulling the drawer release handle see Figure 8 toward the filter access side of the...

Страница 12: ... manual This will help you to identify your unit when dealing directly with United Air Specialists or your local UAS representative 7 1 UNIT CONTROL ON OFF All units will have the blower controlled from the unit control panel refer to Figure 6 A black ON OFF rocker switch is provided to start stop the blower 7 2 CLEANING CONTROLS ON OFF Section 4 4 1 of this manual clearly outlines the available s...

Страница 13: ...r cleaning mechanism Filter elements at end of useful life Open solenoid valve Improper electrical supply Refer to Section 7 for electrical specifications Starter overloadtripped Reset overloads Lack of grease in the rotating socket A The ventilation duct is plugged B Flexible hose not properly connected to arm tubes C The flexible hose is damaged D The Swing Arm damper is closed E Packed filters ...

Страница 14: ...0 V OVERLOAD RELAY 3 PHASE 1 1 2 HP 575 V OVERLOAD RELAY 3 PHASE 3 HP 208 230 V OVERLOAD RELAY 3 PHASE 3 HP 460 575 V CONTROL BOARD CLEANING SYSTEM TRANSFORMER STEP DOWN TO 120V 200 208V TRANSFORMER STEP DOWN TO 120V 230 460V TRANSFORMER STEP DOWN TO 120V 575V SWITCH ROCKER DPST UAS Part No 23 3124 9 23 3124 5 0 23 3124 3 1 23 3124 2 4 23 3124 8 5 23 3124 4 0 20 3232 21 1275 050 21 1274 050 21 127...

Страница 15: ...11 Revised 08 09 V SERIES Cartridge Dust Collector ...

Страница 16: ...IA UAS Part No 45 10017 0001 Item No 11 12 13 14 15 16 18 19 20 General Description VS FILTER COVER ASM GAUGE MINIHELIC 0 5 S P VALVE DIAPHRAGM 1 COMP DM25 W INT SOL DUST DRAWER VS 1500 DUST DRAWER VS750 DISCHARGE HOUSING VS CONTACT UAS FOR AFTER FILTER HOUSING INFORMATION CORD POWER 14 3 W PLUG SJT 15FT SINGLE PHASE POWER CORD POWER 14 3 SJT 15FT 3 PHASE POWER GRIP BLACK VINYL 1 2 ROD SEE STANDAR...

Страница 17: ...lector APPENDIX A V SERIES WRING DIAGRAM Figure 10 Wiring Diagram 120 Volt Single Phase Manual Clean Figure 11 Wiring Diagram 120 Volt Single Phase Pulse Cleaning Figure 12 Wiring Diagram 230 Volt Single Phase Manual Clean 41 2537 41 2538 41 2541 ...

Страница 18: ...14 Revised 08 09 V SERIES Cartridge Dust Collector Figure 14 Wiring Diagram Three Phase Manual Clean w UAS Supplied Starter Figure 13 Wiring Diagram 230 Volt Single Phase Pulse Cleaning 41 2542 41 2543 ...

Страница 19: ...gure 15 Wiring Diagram Three Phase Pulse Cleaning w UAS Supplied Starter Figure 16 Wiring Diagram Three Phase Manual Clean w Customer Supplied Starter 41 2544 Figure 17 Wiring Diagram Three Phase Pulse Cleaning w Customer Supplied Starter 41 2546 41 2545 ...

Страница 20: ...d tear This warranty will be void with respect to equipment that is subject to unauthorized repairs or modifications UAS makes no warranty as to goods manufactured or supplied by others This warranty is subject to any limitations in UAS quotation and may not be modified except by a written instrument signed by the President or Vice President of Sales of UAS THIS WARRANTY IS EXCLUSIVE AND IN LIEU O...

Отзывы: