Visit www.cla-valpacific.com for more details. Contact the Factory at [email protected]
8
8 |
P a g e
Setting the Low and High Level Alarms
1.
Click on ‘Alarms’ on the taskbar
2.
Enter a % value in box highlighted for upper and lower limits for an alarm relay output
3.
Click on ‘Write Alarms’ to upload to the actuator
Diagnostic for the LED
At start-up, the LED remains red for 5 seconds, then switches to blinking green.
Solid Green - Status OK, USB cable connected on the maintenance port.
Blinking Green - Status OK, normal operation
No light - Check 24VDC power supply.
Red – 1. Exceed high torque limit - Power down and power up again.
- 2. Excess voltage (above 32 Volts).
- 3. Update firmware (please wait until update is finished).
Blinking Red/Green – 1. Actuator in calibration mode
- 2. Calibration was not completed correctly - recalibrate.