background image

Visit www.cla-valpacific.com for more details. Contact the Factory at [email protected]

12

12 | 

P a g e

 

 

 

Open your ‘Device Manager’ then plug the Cla-Val USB cable in to your laptop and look under 

‘Ports(COM & LPT) to see which USB Serial Device comes up. (This case it’s COM4) 

 

 

 

Right click on it and select Update driver software. 

 

 

 

Select – ‘Browse my computer for driver software’ option 

 

 

  

 

Содержание CRD-34

Страница 1: ...re details Contact the Factory at info cla valpacific com 1 Setup Guide CRD34 Actuator PACIFIC Visit www cla valpacific com for more details Contact the Factory at info cla valpacific com Set Up Guide...

Страница 2: ...ding d Override 4 20mA Input e Input and Output display 3 Calibrating the 4 20mA Pressure Range Statically 4 5 4 Calibrating the 4 20mA Pressure Range Dynamically 6 7 5 Configuring Actuator On Off Tim...

Страница 3: ...r USB Software and Firmware to your PC Fig 3 5 Download e CPC 34 e Drive 34 Software and Firmware to your PC Fig 4 It is important that you do not allow Windows to install the USB Driver as the cable...

Страница 4: ...of the pressure range Green Circles c The graph shows the current low and high alarm settings Blue Squares 2 Check box Override Setpoint Activated a By typing in a 4 20mA value into the box to the rig...

Страница 5: ...CRA 3 Select Static Calibration from the drop down menu and select the pressure units if required 4 There is a list of spring pressure ratings denoting the pressure change per each 360 Degree adjustme...

Страница 6: ...s immediately to the right of 7 You can also type in your new pressure range in the boxes to the left 8 Click on to write these values to the actuator Done 9 A message will appear Calibration Done Cli...

Страница 7: ...r warning you that you are going into the calibration mode click OK 2 Check the box named CRD CRL CDHS CDB CRA 3 Select Dynamic Calibration from the drop down menu and select the pressure units if req...

Страница 8: ...Loss of Signal 1 Click on Configuration on the task bar 2 To set the Actuator rotation speed enter if not controlled via SCADA enter a time in seconds in each of the windows for time on and time off...

Страница 9: ...actuator Diagnostic for the LED At start up the LED remains red for 5 seconds then switches to blinking green Solid Green Status OK USB cable connected on the maintenance port Blinking Green Status O...

Страница 10: ...and push button Pink 4 20mA Command Signal set point Yellow 4 20mA Command Signal set point Grey Alarm 1 Actuator LOW relay input Brown Alarm 1 Actuator LOW relay output Blue Alarm 2 Actuator HIGH re...

Страница 11: ...the Driver Signature Verification To do this you need to get into the Troubleshooting options from the boot manager Simply select Restart from the power options menu on Windows 8 that s under Charms...

Страница 12: ...n settings you will need to restart your Computer one last time Click Restart Finally you will be given a list of startup settings that you can change The one we are looking for is Disable driver sign...

Страница 13: ...com 12 12 P a g e Open your Device Manager then plug the Cla Val USB cable in to your laptop and look under Ports COM LPT to see which USB Serial Device comes up This case it s COM4 Right click on it...

Страница 14: ...Factory at info cla valpacific com 13 13 P a g e Select Let me pick from a list option Select Have Disk Select C Program Files x86 CLA VAL Multi USB Driver 64 Setup from the drop down menu Or whereve...

Страница 15: ...tory at info cla valpacific com 14 14 P a g e C Program Files x86 CLA VAL Multi USB Driver 64 Setup should now be displaying as below Click OK It should now display as below Click Next This Security W...

Страница 16: ...Interface shown under Universal Serial Bus Controllers each time you connect the Cla Val USB lead PACIFIC AUTOMATIC CONTROL VALVES 45 KENNAWAY ROAD WOOLSTON CHRISTCHURCH 8023 A Cla Val Pacific 45 Ken...

Отзывы: