CLA-VAL 36 Series Скачать руководство пользователя страница 2

Page 2

When the system is drained, the plug will reopen allowing air

to rapidly re-enter the piping system.  See Figure 2.

3.

Sizes 6” & 8” Flanged Parts List 

INSTALLATION

The installation of the valve is important for its proper operation.

Valves must be installed at the system high points in the vertical

position  with  the  inlet  down.    For  pipeline  service,  a  vault  with

freeze  protection,  adequate  screened  venting,  and  drainage

should  be  provided.    During  closure,  some  fluid  discharge  will

occur  so  vent  lines  should  extended  to  an  open  drain  area  in

plant  services.   A  shut-off  valve  should  be  installed  below  the

valve in the event servicing is required.

CAUTION

:   Always Install valve with “INLET” port 

down or flooding will occur.

MAINTENANCE

The Combination Air Valve requires no scheduled lubrication or

maintenance.

INSPECTION: Periodic inspection to verify operation can be per-

formed.  A manual drain valve can be installed in the lower drain

plug to plug to perform this operation as shown in Figure 7.

DRAIN
VALVES

INLET SHUT-OFF
VALVE

FIGURE 5. INSPECTION PIPING

With  the  inlet  shut-off  valve  open,  partially  open  the  drain

valve until flow can be heard.  If the air valve is working prop-

erly, water should be exhausted from the drain valve.  If air

is exhausted, follow steps 2-6.

1.

Close the inlet shut-off valve.

2.

Slowly open the drain valve to allow the fluid in the valve to

drain.  If draining is difficult, the valve may be clogged (valve

requires service). 

3.

Close the drain valve

4.

Slowly open the inlet shut-off valve to fill the valve with water.

Observe the seating action and verify that the valve closes

without leakage.

5.

If leakage occurs, the valve should be removed and inspect-

ed for water or possible damage from foreign matter.

6.

23

24

25

9

4

26

2

6

8

5

1

15

28

9

19

21

30

8A

4A

28

11

7

12

22

34

18

3

13

17

10

5A

INLET

OUTLET

125 LB. FLG.

or

250 LB. FLG.

Detail No.

1

2

3

4

4a

5

5a

6

7

8

8a

9

10

11

Detail No.

12

13

15

17

18

19

21

22

23

24

25

26

28

30

34

Part Name 

Body

Cover

Leverage Frame

Seat

Seat

Float

Float

Gasket

Cover Bolt

Retaining Screw

Retaining Screw

Guide Bushing 

Float Arm

Orifice Button

Part Name 

Pivot Pin

Retaining Ring 

Cushion

Float Retainer

Lock Nut 

Link

Locating Pin

Orifice Button Arm

Hood 

Hood Retaining Screw

Washer - External

Seat Retaining Sleeve

Pipe Plug

Washer

Lock Washer

Содержание 36 Series

Страница 1: ...without dropping Valves should remain boxed clean and dry until installed to prevent weather related damage For long term storage greater than six months the valves must remain in the box and stored indoors Do not expose valves to sunlight or ozone for any extended periods DESCRIPTION OF OPERATION The Combination Air Valve is fully automatic and designed to continuously remove air accumulating at ...

Страница 2: ...N PIPING With the inlet shut off valve open partially open the drain valve until flow can be heard If the air valve is working prop erly water should be exhausted from the drain valve If air is exhausted follow steps 2 6 1 Close the inlet shut off valve 2 Slowly open the drain valve to allow the fluid in the valve to drain If draining is difficult the valve may be clogged valve requires service 3 ...

Страница 3: ...disassembled without removing it from the pipeline Or for convenience the valve can be removed from the line All work on the valve should be performed by a skilled mechanic with proper tools No special tools are required CAUTION The valve must be drained before removing the cover or pressure may be released causing injury Close inlet shut off valve Slowly open drain valve or remove drain plug Remo...

Страница 4: ...ia Ave Costa Mesa CA 92627 Phone 949 722 4800 Fax 949 548 5441 E mail info cla val com www cla val com Copyright Cla Val 2018 Printed in USA Specifications subject to change without notice N 36 Series Single Body R 01 2018 ...

Отзывы: