CLA-VAL 130VC-2 Скачать руководство пользователя страница 4

1) In Calibration Tab mode, click “Calibration Mode” button.  This will allow temporary manual control of actuator for setting new

pilot control limits.  These values will then be sent to actuator at completion of calibration.  Check that actuator LED is
blinking red/green during calibration mode process.  All High and Low point settings steps must be completed in order 
shown.  Use the cancel button to input new values.

2) Look at pressure gauge or flow sensor, use Increase actuator or Decrease actuator buttons until desired LOW pressure or

flow point (same value used in Configuration tab window and showing in Low Point window) is reached.  Press Stop
actuator button to stop actuator.  Use good quality gauges and be as precise as possible.  If calibrating CDHS-32 for flow 
rate using an orifice plate, a calibrated differential pressure gauge or transmitter is recommended.

3) Once desired low pressure or flow is reached and actuator is topped, click Low point setting button.

4) Look at pressure gauge or flow sensor, use Increase actuator or Decrease actuator buttons until desired HIGH pressure or

flow point (same value used in Configuration tab window and showing in High Point window) is reached.  Press Stop 
actuator button to stop actuator.  

5) Once the high pressure or flow is reached and actuator is stopped, click High point setting button.

6) Finally, click Download calibration button to store values in actuator.  High point, Low point, Loss-of-Signal, and Rotation 

speed settings are sent to actuator.  Actuator LED will change to green when complete.  Unplug cable from actuator and 
replace protective cap.  130VC-2 Actuator is now ready to accept 4 - 20 mA command signal from permanent cable Yellow
and Black wires. 

Calibration - Actuator Limits Settings

Fig. 2

Page 4

Содержание 130VC-2

Страница 1: ...r use Consult Cla Val factory technical support if you have questions C The five wire cable is permanently attached to 130VC 2 actuator and should be terminated in suitable junction box for all field...

Страница 2: ...uter for installa tion at a later time click SAVE to save this program 3 This program will automatically be installed in new e Drive folder in C Program Files Cla Val folder on your computer A new Cla...

Страница 3: ...ctuator has power it will do one of the following Go to 4 mA Actuator will decrease pilot setting to 4 mA position Last position Actuator will stay in last position Highly recommended Go to 20 mA Actu...

Страница 4: ...an orifice plate a calibrated differential pressure gauge or transmitter is recommended 3 Once desired low pressure or flow is reached and actuator is topped click Low point setting button 4 Look at p...

Страница 5: ...Look at pressure gauge or flow sensor and use Increase actuator or Decrease actuator buttons to increase pressure or flow as close as is practical to desired HIGH pressure point 3 Enter this value in...

Страница 6: ...red LOW pressure point 3 Enter this value in the projected Low point calibration window 4 Next click on Low point setting button and then click on Download calibration button The actuator automaticall...

Страница 7: ...s into the Turn to low and to high points Numbers must be positive and can contain up to decimal points 7 Click Download Calibration button to complete actuator setup 8 Click cancel button to restart...

Страница 8: ...ween high and low starting points Accuracy of projected values is based on accuracy of initial value and any error will be magnified when projected from starting point Why is actuator LED still blinki...

Отзывы: