9. Range of the flow rate sensor:
Î
Adjust the range of the sensor, if the flow rate sensor
is connected.
See Page 56.
10. Range of the pressure sensor:
Î
Adjust the range of the sensor, if the pressure sensor
is connected.
See Page 56.
Î
Complete the commissioning menu by pres-
sing button 5:
The controller is then ready for operation and normally the
factory settings will give close to optimum operation.
6. Loading store 2:
Î
Switch on or off the “loading store 2” option.
Note:
“Loading store 2” can only be adjusted if a
2-store system or store loading in layers has
been selected in the sub channel ARR.
7. Pump control type:
Î
Adjust the type of pump control for PUMP1
Carry out this adjustment for PUMP2 if needed.
8. Minimum speed:
Î
Adjust the minimum pump speed for PUMP1
In systems with 2 pumps, the adjustment has to be
carried out for PUMP2 as well.
Note:
The minimum speed can only be adjusted if
pulse control (PULS) or PWM control (A, b, C)
has been selected in the sub channel PUMP1,2.
Note:
Description of the pump control type,
see page 46.