5.  Battery Status Menu 

 

 

 

6.  Output Power Menu 

 

7. Temperature Menu 

 

8.  History Record Menu 

 

 

 

 

 

17

 

9.  Bypass Range Set Menu 

A. To protect the load, the function 

of bypass auto-transfer is 

activated only when the AC main 

voltage is within the range of LO 

(low) and HI(high). In this screen, 

press on/off Control Key to enter 

the following steps for LO/HI 

voltage setting. 

 

 

 

B. The cursor (

) will pop up to 

indicate the item newly selected. 

Press on/off Control Key to get 

the item of LO or HI range the 

user want to adjust. 

 

C. Use Up or Down-key to adjust 

the voltage (changing 1V by 

every press). LO (low 

rang):176V+/- 20V, HI(high 

range):253V+/- 20V). 

 

D. Once the value is confirmed, 

press on/off Control Key again to 

save the data. 

 

 

 

 

 

Содержание CPO-S1000

Страница 1: ...O S1000R CPO S2000R CPO S3000R Uninterruptible Power Supply 1 CONTENTS 1 INTRODUCTION 1 2 SAFTY INSTRUCTION 2 3 SYSTEM DESCRIPTION 4 4 CABLE CONNECTION 7 5 OPERATION 8 6 TROUBLE SHOOTING GUIDE 13 7 OP...

Страница 2: ...er 4 If the UPS will be stored for long period the battery must be charged once every 90 days 5 Retain the load within the rating of UPS to prevent faults 6 Handle unusual events according to the trou...

Страница 3: ...nt Please take the precautionary measures specified below and any other measures necessary when working with batteries remove wristwatches rings and other metal objects use only tools with insulated g...

Страница 4: ...shutdown or over temperature 6 Warning LED yellow To indicate the UPS is in the status of overload bypass and battery back up 7 Normal LED green To indicate the UPS is operating normally 3 2 Outline D...

Страница 5: ...9 RS 232 Interface Port 6 Remote Control Mini LCD for LED panel only Option 2 SNMP Intelligent Slot Option 7 Fan 3 Fax Modem Surge Protection 8 External Battery Socket 4 Remote Control Detachable LCD...

Страница 6: ...ker 5 External Battery Socket 10 Output Socket NEMA or IEC 11 2KVA 3KVA Tower Case 1 DB 9 RS 232 Interface Port 7 External Battery Socket 2 SNMP Intelligent Slot Option 8 Remote Control Mini LCD for L...

Страница 7: ...e the nominal amperage of your incoming feeder 3 Inspect the packaging carton and its contents for damage Please inform the transport agency immediately should you find signs of damage Please keep the...

Страница 8: ...beeps twice the UPS will start up and Normal LED lights up to indicate the power is from its inverter to the load 3 When the UPS on off Control Key and the LCD Select Up key are pressed simultaneousl...

Страница 9: ...and HI high In this screen press on off Control Key to enter the following steps for LO HI voltage setting B The cursor will pop up to indicate the item newly selected Press on off Control Key to get...

Страница 10: ...ING GUIDE 6 1 UPS Status and Action The description of the following guideline may be helpful in problem solving 1 LED and LCD status as below UPS STATUS AC utility power is normal UPS is running norm...

Страница 11: ...LED and LCD status as below UPS STATUS AC utility power is normal but the load is supplied by AC utility power via bypass Output power is more than 150 referring to the Output Power Menu Warning LED...

Страница 12: ...ill restart up when AC utility power is restored If AC utility power failure is more than 6 hours please follow storage instruction 23 7 OPERATION MODES OF THE UPS 7 1 UPS System Block Diagram 7 2 Nor...

Страница 13: ...o communicate with the computer Its major functions are as follows 1 To broadcast a warning when power fails 2 To close any open files before the battery exhausted out 3 To turn off the UPS 2 Supply R...

Страница 14: ...d discharge Transfer Time AC fail 0 ms 2 5ms typical from inverter to bypass and vice versa Battery Battery low shutdown and Fuse Overload 125 150 30sec then switch to bypass and auto re transfer 150...

Страница 15: ...76V 253V 20V re settable via LCD panel Transfer Time AC fail 0 ms 2 5ms typical from inverter to bypass and vice versa Battery Mode Beeping every 4 seconds re settable and per second when battery low...

Отзывы: