8
Installation
Connecting 7-th pin connector to power supply
B4 - can be connected to hour meter
S3 – signal for malfunction
T1 & T2 – room thermostat
F3 – Boiler thermostat
Compressed air inlet
Connect a compressed air line to the pressure regulator
Be shore that air pressure is more then 1,5 bar
The primary airflow should be set using the pressure regulator
according to the required burner output. The information
given in the diagram (page 5) can be used as guide values.
Higher-viscosity fuels require higher air pressures
Oil pump
The oil pumps serve as delivery units, pumping oil
into the burner tank. The atomization of the oil is
not dependent on the oil pressure.
Do not increase oil pressure under any
circumstances!
Connect 4 meters of oil pipe between return port
and storage tank
Connect 1 meter of oil pipe between inlet port
and FAG filter 1”
Connect 3 meters of oil pipe between FAG filter
and storage tank
NEWER install inlet oil pipe to take oil from the
bottom of the storage tank! Best solution is to use
floating suction.
All water, sludge and other impurities are on the
bottom! ( they are more heavy then oil )
Drain water from the storage tank once a month
threw drain tap.
Содержание G1p
Страница 1: ...MULTIFUEL oil burners Complyng with EMC 89 336 EC LV 73 23 EC 1...
Страница 5: ...5 JUNIOR Dimensiones...
Страница 6: ...6 Dimensions Gp G1p G2p G2p G3p G3p...
Страница 7: ...7 Dimensions Boiler location Air oil flow schematic...
Страница 12: ...12 Wiring diagram...
Страница 13: ...13 Troubleshooting...
Страница 15: ...15 Burner pump...
Страница 16: ...16 Burner pump...
Страница 21: ...21 Part droving...