18 

Maintenance 

Photo-cell (flame sensor) must be cleaned 
every 30 days. If the photo-cell is dirty, burner  
will start flame and after 4 sec. Control box will 
show malfunction (red light will  appear) 
Be careful to turn the photo cell 
to “see” the flame.  (see picture)  

Depending on the quality of the oil used, we recommend the following maintenance intervals:

 

Monthly: 

• Clean the filter in the supply tank or the unit tank and strainer on the floating suction unit 
• Check the oil level in the supply tank to be shore that enough fuel  is available.  
• Remove and clean the feed pump filter 
• Remove sludge and residual water from the supply tank or unit tank 
• The quantity can be determined by using water indication paste and a gauging rod 
• Clean the photocell 
• Clean the ignition electrodes and flame ring and blow out the nozzle with compressed air, check 
the spacing between the ignition electrodes (refer to checking dimensions for ignition electrodes 
page 14) 
 •The electrode porcelain insulators must be free from carbon, oil, dirt, cracks. Otherwise, short 
circuiting could cause ignition problems. 
 • Check boiler, if it is dirty, clean it. 
 

Annually (before or after the heating period): 

• Carry out monthly maintenance as described 
• Clean the heating cartridges in the burner tank 
• Clean the ignition electrodes and baffle plate, blow out the nozzle with compressed air and check 
the spacing between the ignition electrodes 
• Clean the burner tank, supply tank and unit tank thoroughly. 
• Clean the boiler and chimney.   

Содержание G1p

Страница 1: ...MULTIFUEL oil burners Complyng with EMC 89 336 EC LV 73 23 EC 1...

Страница 2: ...trode adjustment 14 15 Burner pump 15 16 16 Maintenance 17 20 17 Parts drawing 21 18 Parts list 22 19 Main construction parts 23 20 Conformity declaration 24 21 Warranty 25 Read the operation instruct...

Страница 3: ...ne paint thinners or non approved fluids Adequate ventilation must be provided in any enclosure where storage tanks pump or accessories are installed Identical to any gas or oil burning appliance with...

Страница 4: ...s the regulated temperature is reached An additional overheat thermostat prevents overheating A special nozzle draws the fuel by using the passing compressed air which serves as primary air for the co...

Страница 5: ...5 JUNIOR Dimensiones...

Страница 6: ...6 Dimensions Gp G1p G2p G2p G3p G3p...

Страница 7: ...7 Dimensions Boiler location Air oil flow schematic...

Страница 8: ...require higher air pressures Oil pump The oil pumps serve as delivery units pumping oil into the burner tank The atomization of the oil is not dependent on the oil pressure Do not increase oil pressur...

Страница 9: ...be rigidly fastened in place in workmanlike manner NOTE Care must be exercised to ensure leak free connections Flue connection Important condition for perfect operation of the furnace is a correctly d...

Страница 10: ...ng the preventilation time after the safety time The control device may only be plugged in or unplugged if the main switch is in the OFF position or if the 7 pin plug connector is disconnected because...

Страница 11: ...ostat When setting burner for the first time into operation fill burner tank with combustion manual Normal oil level is 50mm from the top If you fill it more overflow switch will turn off burner Secon...

Страница 12: ...12 Wiring diagram...

Страница 13: ...13 Troubleshooting...

Страница 14: ...14 Electrode adjustment It is important to clean electrodes and flame ring monthly to achieve problem free start JUNIOR...

Страница 15: ...15 Burner pump...

Страница 16: ...16 Burner pump...

Страница 17: ...nk Screw back vacuum port screw Unscrew bleed port Turn the burner on When oil arrive close bleed port Maintenance SUPPLY LINES Read this section carefully before installing any supply lines Since a s...

Страница 18: ...The quantity can be determined by using water indication paste and a gauging rod Clean the photocell Clean the ignition electrodes and flame ring and blow out the nozzle with compressed air check the...

Страница 19: ...19 Remote pump Instalation 1 Floater 2 Strainer 3 Flexible oil line 4 Remote pump 5 Oil in the storage tank 6 Burner 7 Combustion chamber 8 Boiler Remote pump 130W Suction unit...

Страница 20: ...m from the top of the heater Ceramic fibre necessary for all burners when used with steel boilers with large combustion chamber or cast iron boilers with a vertical rear panel in the combustion chambe...

Страница 21: ...21 Part droving...

Страница 22: ...tube 21 Flame ring 22 Ignition electrode 23 HT cable 24 Burner tank 25 Heating cartridge 26 Floater 27 Copper pipe 1 28 Burner body lid 29 Overflow tank 30 Contact switch 31 Oil pipe 32 Oil pump 33 So...

Страница 23: ...lator Overheat thermostat Overflow tank Float switch Burner tank Drain tap Oil pump Secondary air regulator Control box Motor Compressed air connection Primary air pressure regulator Solenoid valve Pr...

Страница 24: ...73 23 EC in connection with VDE 0700 part 1 version 04 88 and DIN VDE 0722 version 04 83 Electrical safety according to DIN EN 50 165 2003 and EN 60335 1 2003 Electromagnetic compatibility according...

Страница 25: ...603 1 is used at temperature below 4 C or if winter diesel is used below stipulated temperatures IT IS STRICTLY PROHIBITED TO ADD ANY PETROL The Burners must not be modified or tampered with under cir...