Page 26
Dryer Installation with Multiple Exhaust
For Exhaust Duct less than 14 feet and 2 elbows
equivalent and less than 0.6 inches static pressure.
DRYER EXHAUSTS
Area of section "A-A" must be equal to the sum of dryer exhaust pipes entering muliple exhaust pipe.
(See
chart below.)
MODELS:
L28FD30, L28US30, L36FD30, L36UR30, L36CD36, L44FD42
MODELS:
L28CD30, L28UR30, L36CD30, L36UR30, L36CD36, L44FD42
MODELS:
L44CD42, L50CD42, L52CD48
No. of Dryers
Duct Diameter
(in inches)
(in cm)
No. of Dryers
Duct Diameter
(in inches)
(in cm)
No. of Dryers
Duct Diameter
(in inches)
(in cm)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6 9 11 12 14 15 16 17 18 19 20 21 22 23 23 24 25 26 26 27 28 28 29 30
15 23 27 30 35 38 41 43 46 48 51 53 56 58 58 61 63 66 66 68 71 71 73 76
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
8 12 14 16 18 20 22 23 24 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
20 30 25 41 46 51 56 58 61 66 68 71 73 76 78 81 84 86 89 91 94 97 99 100
1 2 3 4 5 6 7 8 9 10 11 12
12 17 21 24 27 30 32 34 36 38 40 42
30 43 53 61 68 76 81 86 91 97 100 106