Chapter 3 Maintaining the Server
Installing or Replacing Server Components
Installing a Version 1 930W DC Power Supply, UCSC-PSU-930WDC
If you are using a Version 1 930W DC power supply, stripped wires connect power to the removable
connector block. See also
Installing a Version 2 930W DC Power Supply, UCSC-PSU2V2-930DC,
.
Caution
Before beginning this wiring procedure, turn off the DC power source from your facility’s circuit breaker
to avoid electric shock hazard.
Step 1
Turn off the DC power source from your facility’s circuit breaker to avoid electric shock hazard.
Step 2
Remove the DC power connector block from the power supply. (The spare PID for this connector is
UCSC-CONN-930WDC=.)
To release the connector block from the power supply, push the orange plastic button on the top of the
connector inward toward the power supply and pull the connector block out.
Step 3
Strip 15mm (.59 inches) of insulation off the DC wires that you will use.
Note
The recommended wire gauge is 8 AWG. The minimum wire gauge is 10 AWG.
Step 4
Orient the connector as shown in
, with the orange plastic button toward the top.
Step 5
Use a small screwdriver to depress the spring-loaded wire retainer lever on the lower spring-cage wire
connector. Insert your green (ground) wire into the aperture and then release the lever.
Step 6
Use a small screwdriver to depress the wire retainer lever on the middle spring-cage wire connector.
Insert your black (DC negative) wire into the aperture and then release the lever.
Step 7
Use a small screwdriver to depress the wire retainer lever on the upper spring-cage wire connector. Insert
your red (DC positive) wire into the aperture and then release the lever.
Step 8
Insert the connector block back into the power supply. Make sure that your red (DC positive) wire aligns
with the power supply label, “+ DC”.
Step 9
See
Installation Grounding, page 3-68
for additional information about chassis grounding.
Figure 3-32
Version 1 930 W, –48 VDC Power Supply Connector Block
1
Wire retainer lever
2
Orange plastic button on top of the connector
DC
DC
2
1
352024
Содержание UCS C240 M4
Страница 8: ...Contents viii Cisco UCS C240 M4 Server Installation and Service Guide OL 32474 01 ...
Страница 12: ...xii Cisco UCS C240 M4 Server Installation and Service Guide OL 32474 01 ...
Страница 14: ...xiv Cisco UCS C240 M4 Server Installation and Service Guide OL 32474 01 ...
Страница 16: ...xvi Cisco UCS C240 M4 Server Installation and Service Guide OL 32474 01 ...
Страница 26: ...1 10 Cisco UCS C240 M4 Server Installation and Service Guide OL 32474 01 Chapter 1 Overview ...