2-10
Cisco Physical Access Gateway User Guide
OL-32499-01
Chapter 2 Installing and Configuring the Cisco Physical Access Gateway
Installing the Cisco Physical Access Gateway
Step 4
Connect input devices to the Gateway:
a.
Insert two-pin connector plugs into the input ports (see
Figure 2-7
).
b.
(Optional, for supervised input connections only). Install two End-Of-Line (EOL) 1K termination
resistors in each supervised input interface (one terminator in each connector).
Figure 2-6
shows the
terminator installation for a Normally Closed (NC) and Normally Open (NO) input connection.
Figure 2-6
Input Connections: Cisco Physical Access Gateway,Input and Reader Modules
c.
Connect the wires from the input devices (see
Figure 2-7
).
Note
Each of the input connections can be configured as supervised or unsupervised. The tamper and
power fail inputs can be configured as additional unsupervised ports. A supervised input
supports four states: normal, alarm, open and short. An unsupervised input indicates only normal
or alarm.
9
HCRD Hold
Control
HCRD
(blue)
----------
D1/CLCK (white)
10
CP Card
Present
CP
(purple)
----------
D0
(green)
1.
Wire colors are shown in parentheses.
2.
Outputs show the LED color and reader wire color (in parentheses). For example, “GRN (orange)” supports a green LED.
Attach the orange wire from the reader device.
3.
---------- means the wire slot is not used.
Chassis
Label
Description
One Reader
10 Wire Connection
First Reader in a
5 Wire Connection
Second Reader in a
5 Wire Connection
NC
NO
1K,, 1%
1K,, 1%
1K,, 1%
1K,, 1%
187838