b) Install the wing head screws from the internal side of the horizontal plenum as shown in the following
figure.
c) Tighten the screws to a torque value of 11.5 in-lb (1.3 N-m).
Figure 18: Installing the left vertical air plenum
Step 6
Install the vertical air plenum to the right of the horizontal air plenum. Follow steps 5a to 5c.
Figure 19: Installing the right vertical air plenum
Step 7
Install the ANSI 19-inch standard brackets on both sides of the chassis in front position. See
the 19-inch Brackets on the NCS 2002 Shelf for ANSI Rack Configuration
.
Step 8
Install the NCS 2002 empty chassis below the horizontal plenum.
Installing the Air Flow Regulator
15
Installing the Air Flow Regulator
DLP-L70 Installing Air Plenum for NCS 2002 Shelf in ETSI Configuration