background image

Installing the Air Flow Regulator

This chapter explains how to install the regulators to maintain the air flow for ANSI and ETSI configurations
in NCS 2002 shelf.

The air flow within the equipment must be maintained at a nominal temperature. This task can be accomplished
using one of these mechanisms:

• Air deflector
• Air plenum

The sections are:

Air Deflector, on page 1

Air Plenum, on page 1

Air Plenum Rack and Cabinet Compatibility, on page 3

NTP-L42 Install the Air Plenum in NCS 2002 Shelf, on page 4

Air Deflector

An air deflector is a sheet-metal part that is mounted on the NCS 2002 shelf to orient the air flow in a specific
direction.

The air deflectors can be mounted in different positions to control the air flow:

• Front to Front— Only ETSI rack
• Front to Back— For ANSI and ETSI racks
• Front to Top— Only ETSI rack

In an ANSI rack, the air deflectors are mounted only on the 23-inch rack configuration.

Air Plenum

Air plenum orients the air flow in the front-to-back direction inside the equipment to be compliant with GR-63
issue 4 requirement.

NCS 2002 air plenum kit has one horizontal and two vertical air plenums. The air that flows from the front
top inlet are channelized to the right vertical plenum, inside the equipment, and then to the exhaust air channel
towards the left vertical air plenum. The air flow is deflected by 90 degrees and exited out in the rear end.

The following figure shows the air flow inside the air plenum.

Installing the Air Flow Regulator

1

Содержание NCS 2002

Страница 1: ...tion The air deflectors can be mounted in different positions to control the air flow Front to Front Only ETSI rack Front to Back For ANSI and ETSI racks Front to Top Only ETSI rack In an ANSI rack the air deflectors are mounted only on the 23 inch rack configuration Air Plenum Air plenum orients the air flow in the front to back direction inside the equipment to be compliant with GR 63 issue 4 re...

Страница 2: ...he following figures show the dimensions of the air plenum relative to the cabinet or rack Figure 2 Dimension of Cisco NCS 2002 chassis relative to the air plenum Installing the Air Flow Regulator 2 Installing the Air Flow Regulator Air Plenum ...

Страница 3: ...t to back air flow Rack Cabinet Supported 1 ANSI 19 inch rack Supported 1 ANSI 19 inch cabinet Supported ANSI 23 inch rack Supported ANSI 23 inch cabinet Supported 1 ETSI cabinet 1 A minimum opening of 20 600 inches is required to install the vertical air plenum behind the front rails The ANSI 19 inch two post rack that is compatible with air plenum installation is available from Telect with part ...

Страница 4: ...crews ETSI M6 0 x 20 pan head Phillips screws Wing head screws 4 Adapter plates One air plenum kit horizontal and vertical air plenums Tools Equipment As needed Required As Needed Onsite Onsite Remote None Security Level Before performing any of the following procedures ensure that power is removed from the DC circuit Statement 1074 Warning Before working on a chassis or working near power supplie...

Страница 5: ...w points that come in contact so that they are free of paint and other nonconductive coating Apply an appropriate antioxidant compound to the surfaces Warning Procedure Depending on the rack or cabinet complete the necessary task DLP L65 Installing Air Plenum for NCS 2002 Shelf in ANSI 19 inch Configuration on page 5 DLP L69 Installing Air Plenum in NCS 2002 Shelf for ANSI 23 inch Configuration on...

Страница 6: ...he shelf slot in the ANSI 19 inch cabinet or rack Step 2 Insert the wing head screws provided with the kit and tighten to a torque value of 11 5 in lb 1 3 N m Figure 5 Installing the horizontal air plenum in the ANSI 19 inch configuration Step 3 Install the vertical air plenum to the left of the horizontal air plenum a Insert the vertical plenum in the free space between the horizontal plenum and ...

Страница 7: ...ep 5 Install the 19 inch standard brackets on both sides of the chassis in the front position See DLP L35 Mounting the 19 inch Brackets on the NCS 2002 Shelf for ANSI Rack Configuration Step 6 Install the NCS 2002 empty chassis below the horizontal plenum Installing the Air Flow Regulator 7 Installing the Air Flow Regulator DLP L65 Installing Air Plenum for NCS 2002 Shelf in ANSI 19 inch Configura...

Страница 8: ...rews 12 24 x 3 4 pan head Phillips mounting screws 4 Wing head screws 4 Adapter plates One air plenum kit horizontal and vertical air plenum Tools Equipment As needed Required As Needed Onsite Onsite Remote None Security Level The air plenums for ANSI 23 inch configuration can also be pre assembled outside the cabinet and then installed inside the cabinet See DLP L71 Installing Pre assembled Air P...

Страница 9: ...m Figure 9 Installing the adapter plates on the horizontal air plenum Step 3 Place the horizontal air plenum above the shelf slot in the ANSI 23 inch cabinet or rack Step 4 Insert the wing head screws provided with the kit and tighten to a torque value of 11 5 in lb 1 3 N m Installing the Air Flow Regulator 9 Installing the Air Flow Regulator DLP L69 Installing Air Plenum in NCS 2002 Shelf for ANS...

Страница 10: ...tall the wing head screws from the internal side of the horizontal plenum as shown in the following figure c Tighten the screws to a torque value of 11 5 in lb 1 3 N m Figure 11 Installing the left vertical air plenum Step 6 Install the vertical plenum to the right of the horizontal air plenum Follow step 5a to 5c Installing the Air Flow Regulator 10 Installing the Air Flow Regulator DLP L69 Insta...

Страница 11: ... the NCS 2002 Shelf for ANSI Rack Configuration Step 8 Install the NCS 2002 empty chassis below the horizontal plenum Figure 13 Installing the NCS 2002 chassis below the horizontal air plenum Step 9 Return to your originating procedure NTP Installing the Air Flow Regulator 11 Installing the Air Flow Regulator DLP L69 Installing Air Plenum in NCS 2002 Shelf for ANSI 23 inch Configuration ...

Страница 12: ...er plates on the horizontal air plenum Step 2 Align the screws to fix the adapter plates to the shelf Insert the screws and tighten them to a torque value of 11 5 in lb 1 3 N m Step 3 Install the vertical air plenum to the right of the horizontal plenum Step 4 Install the wing head screws from the internal side of the horizontal plenum and tighten the screws to a torque value of 11 5 in lb 1 3 N m...

Страница 13: ... M6 0 x 20 pan head Phillips screws 4 Wing head screws 4 Adapter plates One air plenum kit horizontal and vertical air plenum Tools Equipment As needed Required As Needed Onsite Onsite Remote None Security Level Procedure Step 1 Install the ETSI adapter plates on the horizontal air plenum Step 2 Align the screws to fix the adapter plates to the horizontal air plenum Insert the screws and tighten t...

Страница 14: ...a torque value of 11 5 in lb 1 3 N m Figure 17 Installing the horizontal air plenum in the ETSI configuration Step 5 Install the vertical air plenum to the left of the horizontal air plenum a Insert the vertical plenum in the free space between the horizontal plenum and cabinet Installing the Air Flow Regulator 14 Installing the Air Flow Regulator DLP L70 Installing Air Plenum for NCS 2002 Shelf i...

Страница 15: ...ntal air plenum Follow steps 5a to 5c Figure 19 Installing the right vertical air plenum Step 7 Install the ANSI 19 inch standard brackets on both sides of the chassis in front position See DLP L35 Mounting the 19 inch Brackets on the NCS 2002 Shelf for ANSI Rack Configuration Step 8 Install the NCS 2002 empty chassis below the horizontal plenum Installing the Air Flow Regulator 15 Installing the ...

Страница 16: ...02 chassis below the horizontal air plenum Step 9 Return to your originating procedure NTP Installing the Air Flow Regulator 16 Installing the Air Flow Regulator DLP L70 Installing Air Plenum for NCS 2002 Shelf in ETSI Configuration ...