DETAILED STEPS
Clear the root-cause service-affecting alarm by using one of the following procedures, as appropriate:
•
Clear the LOS (OTS) Alarm, on page 277
•
Clear the LOS (TRUNK) Alarm, on page 279
•
Clear the LOS-P (OCH) Alarm, on page 284
•
Clear the LOS-P (AOTS, OMS, OTS) Alarm, on page 282
•
Clear the LOS-P (TRUNK) Alarm, on page 288
•
Clear the OPWR-LFAIL Alarm, on page 327
If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or call Cisco TAC (1 800 553-2447).
FE-FRCDWKSWBK-SPAN
Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)
Logical Object: STMN
The Far End Forced Switch Back to WorkingSpan condition is raised on a far-end 1+1 protect port when it
is Force switched to the working port.
WKSWBK-type conditions apply only to nonrevertive circuits.
Note
Clear the FE-FRCDWKSWBK-SPAN Condition
SUMMARY STEPS
1.
Complete the
Clear a 1+1 Force or Manual Switch Command, on page 445
procedure for the far-end port.
DETAILED STEPS
Complete the
Clear a 1+1 Force or Manual Switch Command, on page 445
procedure for the far-end port.
If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or call Cisco TAC (1 800 553-2447).
Cisco NCS 2000 series Troubleshooting Guide, Release 11.0
197
Alarm Troubleshooting
FE-FRCDWKSWBK-SPAN