c/en/us/support/interfaces-modules/transceiver-modules/products-device-support-tables-list.html
. To see the
transceiver specifications and installation information, see
http://www.cisco.com/c/en/us/support/
interfaces-modules/transceiver-modules/products-installation-guides-list.html
Statement 1053
—
Class 1M Laser Radition
Class 1M laser radiation when open. Do not view directly with optical instruments.
Warning
Statement 1055
—
Class I and Class 1M Laser
Class I (CDRH) and Class 1M (IEC) laser products.
Warning
Statement 1056
—
Unterminated Fiber Cable
Invisible laser radiation may be emitted from the end of the unterminated fiber cable or connector. Do not
view directly with optical instruments. Viewing the laser output with certain optical instruments (for
example, eye loupes, magnifiers, and microscopes) within a distance of 100 mm may pose an eye hazard.
Warning
Before You Begin
•
The leaf and spine switches must be fully installed in their racks.
•
The leaf and spine switches must be grounded and powered up.
•
If you are using a Cisco Nexus 9504, 9508, or 9516 spine switch in the ACI fabric, it must have only
the 36-port 40-Gigabit ACI-spine I/O modules (N9K-X9736PQ). You cannot mix other I/O modules in
the same chassis when running in ACI mode.
Step 1
For the transceivers with removable cables, make sure that the transceivers are separated from their interface cables.
Step 2
Insert the appropriate transceiver into an active uplink port on the leaf switch.
Step 3
Insert the same type of transceiver in the spine switch port on a X9736PQ I/O module.
Step 4
For transceivers with removable cables, insert the interface cable into the open end of each of those transceivers.
Step 5
Repeat Steps 1 through 4 for each spine switch in the ACI fabric.
The leaf switch is connected to each spine switch in the ACI fabric.
Step 6
Repeat Steps 1 through 5 for each leaf switch in the ACI fabric.
Each leaf switch in the ACI fabric is connected to each spine switch in the network,
What to Do Next
If the APICs are also connected to the leaf switches, then the ACI fabric is ready to be automatically initiated.
Cisco Nexus 9336PQ ACI-Mode Switch Hardware Installation Guide
31
Connecting the Switch to the ACI Fabric
Connecting a Leaf Switch to a Spine Switch