Switch Power Input Requirements
The following table lists the typical amount of power that the switch consumes. It also lists the maximum
amount of power that you must provision for the switch and power supply for peak conditions.
Some power supplies have capabilities that are greater than the maximum power requirements for a switch.
To determine the power consumption characteristics for the switch, use the typical and maximum requirements
that are listed in the following table.
Note
Heat Dissipation
Requirement
Maximum Power
Consumption (AC or DC)
Typical Power
Consumption (AC or DC)
Switch
2415.796 BTUs per hour
708 W
296 W
Cisco Nexus 9332C
Power Specifications
Power specifications include the specifications for each type of power supply module.
750-W AC Power Supply Specifications
These specifications apply to the following power supplies:
• NXA-PAC-750W-PE
• NXA-PAC-750W-PI
Specification
Characteristic
750 W
Maximum output power
10 Amps at 100 VAC
Maximum input current
115 to 240 VAC nominal (Range: 90 to 264 VAC)
Rated input voltage
50 to 60 Hz nominal (Range: 47 to 63 Hz)
Rated input frequency
1100-W AC Power Supply Specifications
These specifications apply to the following power supplies:
• NXA-PAC-1100W-PE
• NXA-PAC-1100W-PI
Cisco Nexus 9332C ACI-Mode Switch Hardware Installation Guide
49
System Specifications
Switch Power Input Requirements