telecommunications equipment in the United States. It is not a legal or regulatory requirement, but rather an
industry requirement.
The following NEBS statements apply to the Firepower 2130:
Statement 7001—
ESD Mitigation
This equipment may be ESD sensitive. Always use an ESD ankle or wrist strap before handling equipment.
Connect the equipment end of the ESD strap to an unfinished surface of the equipment chassis or to the ESD
jack on the equipment if provided.
Note
Statement 7003
—Shielded Cable Shielded Cable Requirements for Intrabuilding Lightning Surge
The intrabuilding port(s) of the equipment or subassembly must use shielded intrabuilding cabling/wiring that
is grounded at both ends.
The following port(s) are considered intrabuilding ports on this equipment:
Gigabit Ethernet management port
RJ-45 1 G/100 M/10 M auto duplex/auto MDI-X Base-T ports
Warning
Statement 7004
—Special Accessories Required to Comply with GR-1089 Emission and Immunity
Requirements
To comply with the emission and immunity requirements of GR-1089, shielded cables are required for the
following ports:
Gigabit Ethernet management port
RJ-45 1 G/100 M/10 M auto duplex/auto MDI-X Base-T ports
Note
Statement 7005
—Intrabuilding Lightning Surge and AC Power Fault
The intrabuilding port(s) of the equipment or subassembly must not be metallically connected to interfaces
that connect to the outside plant (OSP) or its wiring. These interfaces are designed for use as intrabuilding
interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE) and require isolation from the exposed
OSP cabling. The addition of primary protectors is not sufficient protection to connect these interfaces
metallically to OSP wiring.
This statement applies to the intrabuilding ports listed below:
Gigabit Ethernet management port
RJ-45 1 G/100 M/10 M auto duplex/auto MDI-X Base-T ports
Warning
Cisco Firepower 2100 Series Hardware Installation Guide
46
Installation Preparation
Network Equipment-Building System (NEBS) Statements