Cisco 10005 ESR DC Power Entry Module Installation

78-12653-01

Adding or Replacing a DC PEM

Figure 7

Connecting Power to the Terminal Block

Step 6

Insert the power lead from the battery –48V power source into the receptacle 
labeled – (negative) on the PEM. The stripped part of the wire must be fully 
inserted, so that no bare wire is exposed. Use the screwdriver to tighten the 
terminal screw to a torque of 1.5 to 1.8 newton meters (13.28 to 
15.93 inch-pounds). (Tighten the screws clockwise.)

Step 7

If you are connecting a second power source, repeat 

Step 5

 and 

Step 6

 to wire the 

second power source to the second PEM.

Step 8

If your chassis contains only one PEM, install a blank faceplate over the empty 
power bay.

Warning

Blank faceplates (filler panels) serve three important functions: they 
prevent exposure to hazardous voltages and currents inside the chassis; 
they confine electromagnetic interference (EMI) that might disrupt other 
equipment; and they direct the flow of cooling air through the chassis. Do 
not operate the system unless all cards, power modules, and faceplates are 
in place.

CAUTION:

 USE COPPER CONDUCT

ORS ONL

Y

ATTENTION:

 N'UTILISEZ Q

UE DES CONDUCTEURS EN CUR

VE

CAUTION:

 TERMINALS MA

Y BE ENERGIZED

. TURN OFF PO

WER SOURCE CIRCUIT

BREAKER AND REMO

VE PO

WERSUPPL

Y BEFORE A

CCESSING 

TERMINALS

GML

POWER

FAULT

MIS-

WIRE

THIS UNIT HAS MORE 

THAN ONE PO

WER

SUPPL

Y CORD

. DISCONNECT 

TWO (2)

POWER SUPPL

Y CORDS BEFORE

SERVICING 

TO AVOID ELECTRIC SHOCK.

CAUTION

CAUTION:

 USE COPPER CONDUCT

ORS ONL

Y

ATTENTION:

 N'UTILISEZ Q

UE DES CONDUCTEURS EN CUR

VE

CAUTION:

 TERMINALS MA

Y BE ENERGIZED

. TURN OFF PO

WER SOURCE CIRCUIT

BREAKER AND REMO

VE PO

WERSUPPL

Y BEFORE A

CCESSING 

TERMINALS

GML

POWER

FAULT

MISWIRE

THIS UNIT HAS MORE 

THAN ONE PO

WER

SUPPL

Y CORD

. DISCONNECT 

TWO (2)

POWER SUPPL

Y CORDS BEFORE

SERVICING 

TO AVOID ELECTRIC SHOCK.

CAUTION

53628

INPUT
-48/60 V
35A

Содержание DC Power Entry 10005 ESR

Страница 1: ...lation note provides procedures for installing and replacing DC power entry modules PEMs in a Cisco 10005 edge services router ESR Contents The following sections are included in this installation note Product Description page 2 Prerequisites and Preparation page 2 Adding or Replacing a DC PEM page 8 FCC Class B Compliance page 20 Related Documentation page 21 Obtaining Documentation page 22 Obtai...

Страница 2: ...the next section and review the electrical safety and ESD prevention guidelines in the Cisco 10005 ESR Hardware Installation Guide Ensure that you have all of the necessary tools and equipment see the Required Tools and Equipment section on page 7 Have access to the following documents during the installation Technology of Edge Aggregation Cisco 10000 Series Edge Services Router shipped with your ...

Страница 3: ... Before you begin the installation or replacement procedure review the safety guidelines in this section to avoid injuring yourself or damaging the equipment Safety Warnings Safety warnings appear throughout this publication in procedures that if performed incorrectly might harm you A warning symbol precedes each warning statement Before you install configure or perform maintenance on the router r...

Страница 4: ... kunt u het aanhangsel Translated Safety Warnings Vertalingen van veiligheidsvoorschriften in de installatiegids die bij dit toestel is ingesloten raadplegen Varoitus Tämä varoitusmerkki merkitsee vaaraa Olet tilanteessa joka voi johtaa ruumiinvammaan Ennen kuin työskentelet minkään laitteiston parissa ota selvää sähkökytkentöihin liittyvistä vaaroista ja tavanomaisista onnettomuuksien ehkäisykein...

Страница 5: ...ta pubblicazione si trova nell appendice Translated Safety Warnings Traduzione delle avvertenze di sicurezza del manuale d installazione che accompagna questo dispositivo Advarsel Dette varselsymbolet betyr fare Du befinner deg i en situasjon som kan føre til personskade Før du utfører arbeid på utstyr må du være oppmerksom på de faremomentene som elektriske kretser innebærer samt gjøre deg kjent ...

Страница 6: ...trophic power source fault condition hazardous voltages are not present on power terminals and connectors Warning Use copper conductors only Advertencia Este símbolo de aviso significa peligro Existe riesgo para su integridad física Antes de manipular cualquier equipo considerar los riesgos que entraña la corriente eléctrica y familiarizarse con los procedimientos estándar de prevención de acciden...

Страница 7: ... 0 mm thick by 4 0 mm wide An appropriate screwdriver is available from Phoenix Contact Inc of Harrisburg PA USA 1 Wire stripping tool Choose a tool that does not nick the internal wire 2 or 4 Tie wraps 1 Metric measuring tape or ruler 1 Marking pen 1 Voltmeter 3 or 6 length varies 6 AWG recommended copper wires long enough to reach from the Cisco 10005 chassis to the DC power source Three wires t...

Страница 8: ...05 ESR Hardware Installation Guide Installing a Second DC PEM Warning Never install an AC power module and a DC power module in the same chassis Follow these step to install a second DC PEM for redundancy Caution Do not power off the DC PEM that is providing power to the router If you do so all data traffic halts Step 1 Put on an antistatic wrist or ankle strap Connect the strap to the ESD jack on...

Страница 9: ... A A B B NO CO NC NO CO NC EXT CLOCK RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX CAUTIO N USE COPPE R CONDU CTORS ONLY ATTEN TION N UTIL ISEZ QUE DES CONDU CTEUR S EN CURVE CAUTIO N TERMI NALS MAY BE ENER...

Страница 10: ...ile they are touching the power terminals This is an ENERGY HAZARD to you to the voltmeter and to the wires connecting the router to its power source Step 5 Use a screwdriver to loosen the screws on the PEM terminal block and remove the wires Be sure to disconnect the ground bottom wire last Warning When you are installing or replacing the unit the ground connection must always be made first and d...

Страница 11: ...ARM MAJOR ALARM 60 VDC 1A MAX NO CO NC A A B B NO CO NC NO CO NC EXT CLOCK RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX RX TX CAUTIO N USE COPPE R CONDU CTORS ONLY ATTEN TION N UTIL ISEZ QUE DES CONDU CTEUR S EN...

Страница 12: ... and ground wire Figure 4 Trim the end of the insulation so that it is straight as shown in Figure 4 not slanted Figure 4 Stripping Insulation Warning Remove the covering from exactly the specified length of each wire If you strip too much of the covering exposed wire protruding from the terminal block will create an electrical hazard If you strip too little of the covering the wire might not make...

Страница 13: ...ecting DC Ground Warning When you are installing or replacing the unit the ground connection must always be made first and disconnected last To attach the grounding wire to the grounding receptacle on the Cisco 10005 DC PEM perform these steps Step 1 Set the DC PEM power switch to the 0 Off position ...

Страница 14: ... POWER SOURCE CIRCUIT BREAKER AND REMOVE POWERSUPPLY BEFORE ACCESSING TERMINALS GML POWER FAULT THIS UNIT HAS MORE THAN ONE POWER SUPPLY CORD DISCONNECT TWO 2 POWER SUPPLY CORDS BEFORE SERVICING TO AVOID ELECTRIC SHOCK CAUTION CAUTION USE COPPER CONDUCTORS ONLY ATTENTION N UTILISEZ QUE DES CONDUCTEURS EN CURVE CAUTION TERMINALS MAY BE ENERGIZED TURN OFF POWER SOURCE CIRCUIT BREAKER AND REMOVE POWE...

Страница 15: ...er end of the wire is connected to ground at the DC power source Step 8 If you are connecting two power sources to the Cisco 10005 ESR repeat this procedure for the second PEM CAUTION USE COPPER CONDUCTORS ONLY ATTENTION N UTILISEZ QUE DES CONDUCTEURS EN CURVE CAUTION TERMINALS MAY BE ENERGIZED TURN OFF POWER SOURCE CIRCUIT BREAKER AND REMOVE POWERSUPPLY BEFORE ACCESSING TERMINALS GML POWER FAULT ...

Страница 16: ...h their captive screws Step 3 Ensure that the circuit breaker on the newly installed PEM is set to 0 Off Step 4 Turn the and screws on the new PEM s terminal block counter clockwise to fully open the terminal connectors This step ensures that the correct opening is presented for the wires see Figure 5 Step 5 Insert the battery return wire from the external power source into the receptacle labeled ...

Страница 17: ...oltages and currents inside the chassis they confine electromagnetic interference EMI that might disrupt other equipment and they direct the flow of cooling air through the chassis Do not operate the system unless all cards power modules and faceplates are in place CAUTION USE COPPER CONDUCTORS ONLY ATTENTION N UTILISEZ QUE DES CONDUCTEURS EN CURVE CAUTION TERMINALS MAY BE ENERGIZED TURN OFF POWER...

Страница 18: ... Connect the voltmeter s positive contact to the positive terminal on the terminal block Connect the voltmeter s negative contact to the negative terminal on the terminal block If the power is wired correctly The voltmeter registers approximately 48VDC to 56VDC or battery float voltage The yellow Fault LED on the PEM lights Warning Do not allow the test probes of the voltmeter to touch each other ...

Страница 19: ...If the yellow Fault LED on the power module is on Make sure the power switch on the power module is set to On Make sure the power and ground wires are properly connected to the terminals on the PEM Follow the wiring instructions carefully to ensure that you insert the wires into the correct openings in the terminal block See the Wiring a DC PEM section on page 12 for details If the Miswire LED on ...

Страница 20: ...In that event your right to use the equipment might be limited by FCC regulations and you might be required to correct any interference to radio or television communications at your own expense You can determine whether your equipment is causing interference by turning it off If the interference stops it was probably caused by the Cisco equipment or one of its peripheral devices If the equipment c...

Страница 21: ...0 Series ESR 6 Port Channelized T3 Line Card Installation Cisco 10000 Series ESR Channelized STM 1 Line Card Installation Release notes for the Cisco 10000 series ESR These documents which are available at Cisco com are online only Cisco 10000 Series ESR Software Configuration Guide Cisco 10000 Series ESR Troubleshooting Guide Cisco 10000 Series ESR Useful Links Cisco 10000 technical reference doc...

Страница 22: ... www cisco com http www china cisco com http www europe cisco com Documentation CD ROM Cisco documentation and additional literature are available in a CD ROM package which ships with your product The Documentation CD ROM is updated monthly and may be more current than printed documentation The CD ROM package is available as a single unit or through an annual subscription Ordering Documentation Ci...

Страница 23: ...l comments electronically Click Feedback in the toolbar and select Documentation After you complete the form click Submit to send it to Cisco You can e mail your comments to bug doc cisco com To submit your comments by mail use the response card behind the front cover of your document or write to the following address Attn Document Resource Connection Cisco Systems Inc 170 West Tasman Drive San Jo...

Страница 24: ...echnical support download and test software packages and order Cisco learning materials and merchandise Valuable online skill assessment training and certification programs are also available Customers and partners can self register on Cisco com to obtain additional personalized information and services Registered users can order products check on the status of an order access technical support an...

Страница 25: ...al issue by using the TAC online resources Cisco com registered users can open a case online by using the TAC Case Open tool at the following website http www cisco com tac caseopen Contacting TAC by Telephone If you have a priority level 1 P1 or priority level 2 P2 problem contact TAC by telephone and immediately open a case To obtain a directory of toll free numbers for your country go to the fo...

Страница 26: ...ademarks of Cisco Systems Inc Changing the Way We Work Live Play and Learn Discover All That s Possible and Empowering the Internet Generation are service marks of Cisco Systems Inc and Aironet ASIST BPX Catalyst Cisco the Cisco Certified Internetwork Expert logo Cisco IOS the Cisco IOS logo Cisco Systems Cisco Systems Capital the Cisco Systems logo Enterprise Solver EtherChannel EtherSwitch FastH...

Отзывы: