Installing the Controller

This chapter provides procedures for installing the Cisco Catalyst 9800-40 Wireless Controller on an equipment
shelf, tabletop, or in an equipment rack.

Installation Methods, on page 1

Guidelines for a Standalone Equipment Shelf or Tabletop Installation, on page 2

Installing the Controller on a Standalone Equipment Shelf or Tabletop, on page 2

Guidelines for Rack Installation, on page 3

Attaching Front Rack-Mount Brackets, on page 4

Attaching Rear Rack-Mount Brackets, on page 5

Mounting the Controller in the Rack, on page 6

Attaching the Cable Management Bracket, on page 10

Chassis Ground Connection, on page 12

Connecting Cables, on page 14

Management Ethernet Port Cable Connection, on page 15

Installation Methods

The Cisco Catalyst 9800-40 Wireless Controller s are designed for standalone, 2-rail 19-inch rack-mount
(front rail only), and 4-rail 19-inch rack-mount (front and rear rail) installations.

Although rack-mounting is the preferred method of installation, you can mount the chassis on an equipment
shelf or tabletop.

Read the installation instructions before using, installing or connecting the system to the power source.

Statement 1004

Warning

Proceed with the installation, if you have already unpacked your chassis and read all the site requirements for
your new equipment.

Note

Installing the Controller

1

Содержание Catalyst 9800-40

Страница 1: ... Management Bracket on page 10 Chassis Ground Connection on page 12 Connecting Cables on page 14 Management Ethernet Port Cable Connection on page 15 Installation Methods The Cisco Catalyst 9800 40 Wireless Controller s are designed for standalone 2 rail 19 inch rack mount front rail only and 4 rail 19 inch rack mount front and rear rail installations Although rack mounting is the preferred method...

Страница 2: ... install it on the front of the chassis Ensure that an adequate chassis ground earth connection exists for your controller chassis see the Attaching a Chassis Ground Connection section Installing the Controller on a Standalone Equipment Shelf or Tabletop Step 1 Remove any debris and dust from the tabletop or platform as well as the surrounding area Step 2 Lift the chassis into position on the equi...

Страница 3: ...a particular rack check for obstructions such as a power strip that could impair the rack mount installation If a power strip does impair a rack mount installation remove the power strip before installing the chassis and then replace it after the chassis is installed Allow sufficient clearance around the rack for maintenance If the rack is mobile you can push it back near a wall or cabinet for nor...

Страница 4: ...ack Dimensions Step 1 Mark and measure the distance between two holes on the left and right mounting rails The distance should measure 18 31 inches 0 06 inches 46 5 cm 0 15 cm Measure for pairs of holes near the bottom middle and top of the equipment rack to ensure that the rack posts are parallel Note Step 2 Measure the space between the inner edges of the left front and right front mounting flan...

Страница 5: ...ssis The following figure shows where to attach the front rack mount brackets to the Cisco Catalyst 9800 40 Wireless Controller Figure 2 Attaching the Front Rack Mount Brackets to the Cisco Catalyst 9800 40 Wireless Controller Front rack mount bracket screws 3 Front rack mount bracket ear and holes 1 Front rack mount bracket 2 Step 2 Position the front rack mount bracket top hole with the chassis ...

Страница 6: ...ack mount bracket screws 3 Rear rack mount bracket ear and holes 1 Rear rack mount bracket 2 Step 2 Position the rear rack mount bracket with the chassis Step 3 Insert the black screws on one side Do not fully tighten the screws The rear bracket holes are slotted to allow for adjustment Do not fully tighten the screws until the chassis is installed in the four post rack Step 4 Repeat Step 1 to Ste...

Страница 7: ...Align the mounting bracket holes with the rack post holes and attach the chassis to the rack Step 6 Position the chassis until the rack mounting flanges are flush against the mounting rails on the rack To allow space to attach the cable management brackets to the chassis in the rack easily use the rack mount bracket ear holes mentioned in Steps 7 and 8 Tip Step 7 Hold the chassis in position again...

Страница 8: ...aise the front of the chassis to align the mounting bracket holes with the rack post holes while allowing the bottom of the chassis to rest on the shelf Note Step 2 With two people lift the chassis into position between the rack posts Step 3 Position the chassis until the rack mounting flanges are flush against the mounting rails on the rack Use the second hole up from the bottom of the rack mount...

Страница 9: ...ont rack mount bracket ear and screws 3 Rear rack equipment rail 1 Front rack equipment rail 4 Rear rack mount bracket ear and screws 2 Step 7 Use a level to verify that the tops of the two brackets are level or use a measuring tape to verify that both brackets are the same distance from the top of the rack rails What to do next This completes the procedure for installing the chassis in the rack P...

Страница 10: ...nt bracket to the rack mount bracket on one side of the Cisco Catalyst 9800 40 Wireless Controller The cable management bracket aligns to the top hole of the chassis rack mount bracket Step 2 Using a Phillips screwdriver insert one screw through the top screw hole of the cable management bracket and into the chassis rack mount bracket and tighten the screw Use the package of screws that came with ...

Страница 11: ...Chassis front rack mount bracket 3 Cable management bracket U feature 1 Cable management bracket screw holes 2 Step 3 Insert the cable management screw into the screw hole of the cable management bracket and into the chassis rack mount bracket and tighten the screw using a Philips screwdriver Step 4 Repeat step 1 to step 3 for the other side of the chassis Installing the Controller 11 Installing t...

Страница 12: ...lling or replacing the unit the ground connection must always be made first and disconnected last Statement 1046 Warning Have the recommended tools and supplies available before you begin this procedure Recommended Tools and Supplies Use copper conductors only Statement 1025 Warning The following tools equipment and supplies are necessary to connect the system ground to the chassis Philips screwdr...

Страница 13: ...e two screws through the holes in the grounding lug The following figure shows how to attach a grounding lug to the chassis ground connector Figure 9 Attaching the Grounding Lug to the Ground Connector of the Cisco Catalyst 9800 40 Wireless Controller Ground connector on the chassis 3 Chassis ground lug 1 Ground symbol 4 Grounding screws 2 Step 6 Use the Number 2 Philips screwdriver to carefully t...

Страница 14: ...o pin 6 and so on You can identify a crossover cable by comparing the two modular ends of the cable Hold the cable ends in your hand side by side with the tabs at the back Ensure that the wire connected to the outside left pin of the left plug pin 1 is the same color as the wire connected to the outside right pin of the right plug pin 8 The console port is an asynchronous serial port devices conne...

Страница 15: ... Type B connectors are easily confused with 5 pin mini USB Type B connectors Note that only the 5 pin mini USB Type B is supported Note The default parameters for the console port are 9600 baud 8 data bits no parity and 1 stop bit For operation with a Microsoft Windows OS version older than Windows 7 the Cisco Windows USB Console Driver must be installed on any PC connected to the console port If ...

Страница 16: ...Step 2 Insert the other end of the RJ 45 cable to your management device or network Installing the Controller 16 Installing the Controller Management Ethernet Port Cable Connection ...