Cisco ASR 9006 Clearance Requirements
To install a Cisco ASR 9006 Router in a 4-post enclosed cabinet:
• The front and rear doors of the cabinet must be removed or be perforated with a minimum open area of
70 percent. In addition, the right side panel must be removed or perforated with a minimum of 65 percent
open area (70 percent for 800-mm racks).
• There must be a minimum unobstructed space of 6 inches (15.24 cm) between the router’s right side air
inlet and the adjacent wall or cabinet side panel, and a minimum unobstructed space of 6 inches (15.24
cm) between adjacent cabinets. In addition, there should be no exhaust from any source blowing into the
right side panel of the cabinet.
• Rear chassis clearance: Minimum of 2.50 inches (6.40 cm) of clearance.
• Sides chassis clearance: Minimum of 6 inches (15.24 cm) of clearance on the right side of the chassis
(as viewed from the front). There is no clearance requirement for the left side of the chassis.
This figure shows the side and rear chassis air-flow clearance requirements for mounting the Cisco ASR 9006
Router in a 4-post enclosed rack.
Cisco ASR 9000 Series Aggregation Services Router Hardware Installation Guide
19
Preparing for Installation
Cisco ASR 9006 Clearance Requirements