Chapter 5 Troubleshooting the Installation
Troubleshooting Overview
5-4
Cisco 12010, Cisco 12410, and Cisco 12810 Router Installation and Configuration Guide
OL-11496-01
Identifying Startup Issues
shows the contents of the alphanumeric displays on the RP and the line
cards, as well as the normal LED states on the alarm card, the power entry
modules (AC or DC), and the blower module after a successful system startup.
Table 5-1
Alphanumeric Displays and LEDs at System Startup
Component
Type of Indicator
Display Contents/LED Status and Meaning
RP
Alphanumeric
display
Top row: MSTR
Bottom row: GRP or PRP
The RP is enabled and recognized by the system; a valid
Cisco IOS software image is running.
Line Cards
Alphanumeric
display
Top row: IOS
Bottom row: RUN
The line card is enabled and ready for use.
Alarm Display
Detected alarm
severity
MBUS (Alarm A and
Alarm B cards)
CSC 0 and 1
SFC 0, 1, 2, 3, and 4
Critical: Off
Major: Off
Minor: Off
Enabled: On
Fail: Off
Enabled: On
Fail: Off
Enabled: On
Fail: Off
2400 Watt AC
and DC Power
Supplies
Power status
Pwr OK: On
Fault: Off
Temp: Off
Ilim: Off (AC-input power supplies only)
The correct power module voltages are present and no faults
have been detected.