Instruction Manual

Wibeee

 SAFETY PRECAUTIONS

DANGER

Warns of a risk, which could result in personal injury or material damage.

ATTENTION

Indicates that special attention should be paid to a specifi c point.

Follow the warnings described in this manual with the symbols shown below.

If you must handle the unit for its installation, start-up or maintenance, the following 

should be taken into consideration:

Incorrect handling or installation of the unit may result in injury to personnel as well as damage 

to the unit. In particular, handling with voltages applied may result in electric shock, which may 

cause death or serious injury to personnel. Defective installation or maintenance may also 

lead to the risk of fi re.

Read the manual carefully prior to connecting the unit. Follow all installation and maintenance 

instructions throughout the unit’s working life. Pay special attention to the installation stan-

dards of the National Electrical Code.

Refer to the instruction manual before using the unit

In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can 

result in injury or damage to the unit and /or installations.

CIRCUTOR, SA reserves the right to modify features or the product manual without prior notifi cation.

 DISCLAIMER

CIRCUTOR, SA

 reserves the right to make modifi cations to the device or the unit specifi ca-

tions set out in this instruction manual without prior notice. 

CIRCUTOR, SA

 on its web site, supplies its customers with the latest versions of the device 

specifi cations and the most updated manuals.                                 

 

 

 

 

 

 

           www.circutor.com

CIRCUTOR, 

recommends using the original cables and accessories that are 

supplied with the device.

Содержание WIBEEE Series

Страница 1: ...INSTRUCTION MANUAL Consumption analysers M064B01 03 20A SMART PLUGGING ...

Страница 2: ...2 Wibeee Instruction Manual ...

Страница 3: ...ly prior to connecting the unit Follow all installation and maintenance instructions throughout the unit s working life Pay special attention to the installation stan dards of the National Electrical Code Refer to the instruction manual before using the unit In this manual if the instructions marked with this symbol are not respected or carried out correctly it can result in injury or damage to th...

Страница 4: ... OPERATION 18 4 1 OPERATING PRINCIPLE 18 4 2 MEASUREMENT PARAMETERS 18 4 2 1 Wibeee M L and Wibeee M R 18 4 2 2 Wibeee T L Wibeee T R and Wibeee 3P 19 4 3 LED INDICATORS 19 4 4 BUTTON 20 4 5 START UP 20 5 DISPLAY AND CONFIGURATION 22 5 1 MOBILE APPLICATION 22 5 2 WEB PLATFORM 23 5 2 1 HOME 24 5 2 2 DASHBOARD 28 5 2 3 DEVICES 29 5 2 4 NOTIFICATIONS 29 5 2 5 REPORTS 30 5 2 6 HELP 32 5 3 INTERNAL WEB...

Страница 5: ...5 Instruction Manual Wibeee 9 WARRANTY 46 10 CE CERTIFICATE 47 ...

Страница 6: ...f the devices are for illustration purposes only and may differ from the orig inal device SYMBOLS Table 2 Symbols Symbol Description Compliant with the relevant European standards Do not remove from hazardous live conductors or place it around them Double insulation AC current Device covered by European directive 2002 96 EC At the end of its useful life do not leave the device in a household waste...

Страница 7: ...atented DINZERO system and consists of simply attaching the de vice to the cable or to the upper part of an MCB miniature circuit breaker Once switched on the device will begin to convert the measured parameters into information that is sent via a wireless connection There are 5 models available Wibeee M L single phase model with a neutral connection on the left Wibeee M R single phase model with ...

Страница 8: ...ntial to keep the cables in a perfect condition to avoid accidents personal injury and damage to installations Limit the operation of the device to measuring the specified current or voltage values The manufacturer of the device shall not be held responsible for any damage resulting from the user or installation company failing to observe the warnings and or recommendations indicated in this manua...

Страница 9: ...protective equipment The device should be installed after the circuit breaker Imax 63 A To install the device carry out the following steps 1 Remove the protective panel from the electric panel Figure 1 Remove the connection panel 2 When installing the device make sure that the neutral terminal N corresponds with the neu tral cable of the installation your device could be damaged if incorrectly in...

Страница 10: ...inking 3 3 DEVICE TERMINALS 3 3 1 Wibeee M L Table 3 List of terminals of the Wibeee M L Terminals of the Wibeee M L device 1 N Neutral 2 L1 Voltage input 1 2 Figure 3 Wibeee M L Terminals 3 3 2 Wibeee M R Table 4 List of terminals of the Wibeee M R Terminals of the Wibeee M R device 1 L1 Voltage input 2 N Neutral 1 2 Figure 4 Wibeee M R Terminals ...

Страница 11: ...1 N Neutral 3 L2 Voltage input L2 2 L1 Voltage input L1 4 L3 Voltage input L3 1 2 3 4 Figure 5 Wibeee T L Terminals 3 3 4 Wibeee T R Table 6 List of terminals of the Wibeee T R Terminals of the Wibeee T R device 1 L1 Voltage input L1 3 L3 Voltage input L3 2 L2 Voltage input L2 4 N Neutral 1 2 3 4 Figure 6 Wibeee T R Terminals ...

Страница 12: ...st of terminals of the Wibeee 3P Terminals of the Wibeee 3P device 1 L1 Voltage input L1 3 L3 Voltage input L3 2 L2 Voltage input L2 1 2 3 L2 L3 Figure 7 Wibeee 3P Terminals 3 4 CONNECTION DIAGRAMS 3 4 1 Wibeee M L N L Figure 8 Wibeee M L connection diagram ...

Страница 13: ...13 Instruction Manual Wibeee 3 4 2 Wibeee M R N L Figure 9 Wibeee M R connection diagram 3 4 3 Wibeee T L N L1 L2 L3 Figure 10 Wibeee T L connection diagram ...

Страница 14: ...14 Wibeee Instruction Manual 3 4 4 Wibeee T R N L1 L2 L3 Figure 11 Wibeee T R connection diagram 3 4 5 Wibeee 3P L1 L2 L3 Figure 12 Wibeee 3P connection diagram ...

Страница 15: ...ecessary to connect it to one of the first 11 Wi Fi channels The Wibeee s data can be accessed in two ways Application mode Direct share mode 3 5 1 APPLICATION MODE In application mode the data measured by the Wibeee is uploaded to the cloud and accessed using the Wibeee CIRCUTOR application When using this mode the Wibeee and the user who has configured it are linked so the user can control the d...

Страница 16: ...ill send the data If you configure a Wibeee while using this mode there is no link between the user and the device so the only way to access the device when it is connected to the network is by knowing its IP address and accessing it using a search tool To start the device in direct share mode follow these steps 1 On a smartphone tablet use the Wi Fi connection s settings to connect to the Wibeee ...

Страница 17: ...a cur rent clamp and enter the value on the calibration screen Figure 13 Note calibration should be performed when the device has a current flow of 5 10 A Figure 13 Calibration screen 2 Repeat the calibration process for each of the device s measurement cables If you skip the calibration process while installing the device the accuracy of the measurements is not guaranteed If the measurement cable...

Страница 18: ...ibeee CIRCUTOR application or the http wibeee circutor com web platform Direct share mode In direct share mode the Wibeee s data is directly accessed from the device s integrated web server Note The device s integrated web server can also be accessed in the application s operating mode 4 2 MEASUREMENT PARAMETERS The device measures and logs the following parameters 4 2 1 Wibeee M L and Wibeee M R ...

Страница 19: ...he Wibeee T L Wibeee T R and Wibeee 3P Parameter Units Phases L1 L2 L3 Total Voltage V Current A Frequency Hz Active Power kW Apparent Power kVA Inductive Reactive Power kvarL Capacitive Reactive Power kvarC Power Factor PF Active Energy kWh Reactive Energy kvarh Inductive Reactive Energy kvarLh Capacitive Reactive Energy kvarCh Cost CO2 Emissions KgCO2 4 3 LED INDICATORS The device has 2 status L...

Страница 20: ... different states 1 Configuration state Blue LED Slow blinking light 1s Red LED Slow blinking light 1s In this state the Wibeee generates its own Wi Fi network called WIBEEE_xx xx xx It is only used to configure the device and connect it to the user s network If you want to return to this state to obtain the initial conditions you should hold down the Re set button for more than 6 seconds The devi...

Страница 21: ... has connected to the Wi Fi network and is waiting to complete the first successful transfer of data When it first manages to successfully send data it will enter the Connected and sending OK state If the device is not able to successfully send the first set of data it will retry 3 times If it does not manage to send it the Wi Fi connection is restarted and it retries sending the package 3 times I...

Страница 22: ...hare mode Internal Web server Web platform http wibeee circutor com Mobile application Wibeee Circutor Internal Web server Data display Figure 17 Data display based on the operating mode 5 1 MOBILE APPLICATION The Wibeee Circutor mobile application is compatible with iOS and Android and has a version for smartphones and tablets In it you can view and configure all of the parameters measured by the...

Страница 23: ... can access the different sections of the platform Home summary of consumption displays charts and gives access to the dashboard configuration options graphical interface Dashboard displays all of the dashboards of every active device Devices access to all of the connected devices Notifications displays the notifications log Reports access to regular report generation Help help screen ...

Страница 24: ...O2 emissions from the previous month the current month and the forecast for the end of the month It also displays the set target value Figure 20 Summary area The area in Figure 21 shows 2 of the possible charts that can be viewed Table 8 and Table 9 show all of the parameters that can be graphically displayed Use the arrows to toggle between charts ...

Страница 25: ...e latest measurements sent by the device Figure 22 Measurements area In the area in Figure 23 you can access the configuration options for the devices and dashboard see 5 2 1 1 Configuration screen for the devices dashboard Figure 23 Access to the device dashboard configuration area ...

Страница 26: ...owing data DEVICE Figure 24 Configuration screen Device The device s basic data is entered in this section Name The name of the device Select Dashboard Dashboard selection Mac MAC address of the device 2 4 Quadrants Measurement selection for 2 quadrants consumption or 4 quadrants consumption and generation LOCATION Figure 25 Configuration screen Location ...

Страница 27: ...n of the device COST Figure 26 Configuration screen Cost The costs are entered in this section Price kWh Price of kWh Tax Other Tax Fees and taxes Other Costs Cost day Other costs Cost kW Day Cost kW Day Cost in kW per day Billing date Billing date Contracted power kW Contracted power TARGET AND NOTIFICATIONS Figure 27 Configuration screen Target and Notifications ...

Страница 28: ...rvoltage 253 V for more than one minute in the last hours 253V t 1 min Undervoltage Wibeee has detected a undervoltage 207 V for more than one minute in the last hours 207V t 1 min High consumption alarm for high consumption in the installation with the current consumption the limit established in the Wibeee will be exceeded at the end of the month 5 2 2 DASHBOARD The Dashboard screen Figure 28 sh...

Страница 29: ...Devices screen Figure 30 displays a list of all of the connected devices Figure 30 Devices screen 5 2 4 NOTIFICATIONS The Notifications screen Figure 31 shows a log of all of the notifications that have been generated Figure 31 Notifications screen ...

Страница 30: ...ports screen Figure 32 is divided into two areas Figure 32 Reports Screen REPORTS This section shows the scheduled reports to be regularly generated To create a new regular report press the icon The dialogue box in Figure 33 opens Figure 33 New Report ...

Страница 31: ...ing period Recipients Enter the email addresses of the recipients of the report You can prepare a simple version of a report by selecting Normal Section Figure 33 where everything is pre configured and you only have to select the quantity Or an advanced version by selecting Advanced Section Figure 34 where you can configure a lot more options Figure 34 New Report Advanced Section REPORT LOG In thi...

Страница 32: ...b platform and application of the two Wibeee systems Figure 35 Help Screen 5 3 INTERNAL WEB SERVER Figure 36 shows the screen where you access the device s internal web server The device s default address is http 192 168 1 150 User user Password user Figure 36 Internal web server access screen The main screen is shown in Figure 37 ...

Страница 33: ... Manual Wibeee Figure 37 Main screen of the internal web server 5 3 1 INSTANT DATA In this section you can access instant data from each of the measurement phases Figure 38 Figure 38 Internal web server Instant Data ...

Страница 34: ... the network parameters in the Network section Figure 39 Figure 39 Internal web server Network 5 3 3 ADVANCED OPTIONS You can configure the IP parameters in the Advanced Options section Figure 40 Figure 40 Internal web server Advanced Options wibeee circutor com ...

Страница 35: ...ergy meter by pressing the button 5 4 CONFIGURATION THROUGH HTTP GET REQUESTS Wibeee accepts HTTP GET requests for parameter and settings queries for the device Requests must be made directly to the IP address 192 168 1 150 after connecting to the Wi Fi network created by the device All requests made to the Wibeee s internal server are GET requests and when they have been processed by the server i...

Страница 36: ...able variables http ip_address services user values xml var device variable Figure 43 HPPT queries Values of the device s variables Table 11 Variables table Variable Description Units var measuresRefresh var Measures refresh time of the internal web Seconds var appRefresh var Time sending data to the server Minutes var softVersion var Firmware version of the device var model var Model identifier v...

Страница 37: ...2 L3 A var pap1 var Apparent Power L1 VA var pap2 var Apparent Power L2 VA var pap3 var Apparent Power L3 VA var papt var Total Apparent Power VA var pac1 var Active Power L1 W var pac2 var Active Power L2 W var pac3 var Active Power L3 W var pact var Total Active Power W var preac1 var L1 Reactive Power Var var preac2 var L2 Reactive Power Var var preac3 var L3 Reactive Power Var var preact var T...

Страница 38: ... name WIBEEE dhcp false ip c0a80196 gw c0a80101 subnet ffff0000 id 0 5973659041337669 Table 12 Configuration HPPT variables Request 1 Variable Description name Name of the Wibeee dhcp false static network true dynamic network ip IP address in hexadecimal gw Gateway in hexadecimal subnet Subnet mask in hexadecimal 2 Configuration of the Local Wi Fi Network http ip _address config_value ssid Cirprot...

Страница 39: ...onfiguration http ip_address conFigure_server URLServidor c339a462 portServidor 1f91 id 0 33531335316222393 Table 15 Configuration HPPT variables Request 4 Variable Description ServerURL Name of the server domain Serverport Port in hexadecimal 5 Resetting the device http ip_address config_value reset true id 0 03616242413409054 ...

Страница 40: ...f wireless devices in a spe cific organisation airport hospital etc it is advisable to ask for authorisation to use wireless communications 6 2 Wi Fi COMMUNICATIONS Wi Fi is one of the most widely used wireless technologies today for connecting and exchang ing information between electronic devices without having to connect them physically The Wibeee has Wi Fi communications in the 2 4 GHz band co...

Страница 41: ...se Three phase Frequency L2 Freq2x10 0007 Hz x 10 Three phase Frequency L3 Freq3x10 0008 Hz x 10 Three phase Total Frequency FreqTx10 0009 Hz x 10 Single phase Three phase Active Power L1 Wreal1x10 000A W x 10 Single phase Three phase Active Power L2 Wreal2x10 000B W x 10 Three phase Active Power L3 Wreal3x10 000C W x 10 Three phase Total Active Power WrealTx10 000D W x 10 Three phase L1 Reactive ...

Страница 42: ...phase Inductive Reactive Energy L3 EreactL3 0026 0027 kVarh Three phase Total Inductive Reactive Energy EreactLT 0028 0029 kVarh Three phase Capacitive Reactive Energy L1 EreactC1 002A 002B kVarh Single phase Three phase Capacitive Reactive Energy L2 EreactC2 002C 002D kVarh Three phase Capacitive Reactive Energy L3 EreactC3 002E 002F kVarh Three phase Total Capacitive Reactive Energy EreactCT 003...

Страница 43: ...ent margin Wibeee M x Wibeee T x Wibeee 3P 1 65 A 1 65 A Min current measurement Istart 500 mA 500 mA Installation category CAT III CAT III Measurement accuracy Voltage measurement 2 variations in range of use at PF 1 Current measurement 2 variations in range of use Power measurement 4 variations in range of use Variations in Range of Use Magnitude of influence Range of influence Typical Maximum T...

Страница 44: ...ction degree IP20 Insulation Double insulation Mechanical features Dimensions mm Wibeee M x Wibeee T x Wibeee 3P Figure 44 Figure 45 Figure 46 Weight 37 g 64 g 53 g Surround Self extinguishing VO Plastic UNE 21031 90ºC 49 50 5 28 20 22 Figure 44 Dimensions Wibeee M L and Wibeee M R 80 50 5 28 20 22 Figure 45 Dimensions Wibeee T L y Wibeee T R 47 87 53 40 49 Figure 46 Dimensions Wibeee 3P ...

Страница 45: ...ing circuits UNE EN 61010 2 030 Electrical equipment for measurement control and laboratory use EMC requirements Part 1 General requirements IEC 61326 1 2005 UNE EN 61326 1 Electromagnetic compatibility and Radio spectrum Matters ERM Elec troMagnetic Compatibility EMC standard for radio equipment Part 17 Specific conditions for Broadband Data Transmission Systems EN 301 489 17 V2 2 1 ...

Страница 46: ...con trary to the national electrical code or that surpasses the limits indicated in the technical and environmental features of this manual CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the installation nor will it cover any possible sanctions derived from a pos sible failure improper installation or improper usage of the unit Consequently this guarantee do...

Страница 47: ...47 Instruction Manual Wibeee 10 CE CERTIFICATE ...

Страница 48: ...48 Wibeee Instruction Manual ...

Страница 49: ...49 Instruction Manual Wibeee ...

Страница 50: ...CIRCUTOR SA Vial Sant Jordi s n 08232 Viladecavalls Barcelona Tel 34 93 745 29 00 Fax 34 93 745 29 14 www circutor com central circutor com ...

Отзывы: