40
Wibeee Max
Instruction Manual
Table 17 (Cont�): Modbus memory map�
Parameter
Symbol
Address
Units
Capacitive Reactive Energy L1
EreactC1
002A - 002B
kVarh
Capacitive Reactive Energy L2
EreactC2
002C - 002D
kVarh
Capacitive Reactive Energy L3
EreactC3
002E - 002F
kVarh
Total Capacitive Reactive Energy
EreactCT
0030 - 0031
kVarh
Function 05
is used to delete energy meters.
Table 18:Modbus memory map: Deleting parameters
Deleting parameters
Address
Value to be sent
Deleting energy meters
0000
0xFF00