Instruction Manual
Table 8: Variations in range of use�
Variations in range of use
Magnitude of Influence
Range of influence
Typical
Maximum
Temperature
- 10ºC ... +60ºC
-
±0.3 % / ºC
Relative humidity
10% ... 90%
-
0.3 %
Conductor position
-
2 %
3 %
Adjacent conductor
D/4 300 A
-
2 %
Set to 50 Hz
Full scale
0.2 %
0.3 %
Set to 60 Hz
Full scale
0.2 %
0.3 %
Frequency
40 Hz - 5 kHz
< ± 1 dB
< ± 1 dB
Deviation 50 Hz - 60 Hz
-
-
0.3 %
3�3�2�1�- Scale selection
The
FLEX Wibeee 54
current sensors indicate the selected scale through the
blue
and
red
LEDs on their head.
During the first 20 seconds after being switched on, the
Wibeee Max Plus
is in the scale selec-
tion period. The
blue
and
red
LEDs flash slowly and indicate the selected scale.
Press the
RESET
key during this period to select the desired scale:
The
blue
LED indicates that the
100 A
scale has been selected.
The
red
LED indicates that the
1 kA
scale has been selected.
The
blue
and
red
LEDs indicate that the
5 kA
scale has been selected.
When the scale selection period has ended, the quick blinking light is deactivated and the
blue
and
red
LEDs indicate the selected scale.
Содержание Wibeee Max
Страница 1: ...INSTRUCTION MANUAL Consumption analysers M169B01 03 18A ...
Страница 2: ...2 Wibeee Max Instruction Manual ...
Страница 44: ...44 Wibeee Max Instruction Manual 10 CE CERTIFICATE ...
Страница 45: ...45 Instruction Manual Wibeee Max ...
Страница 46: ...46 Wibeee Max Instruction Manual ...
Страница 47: ...47 Instruction Manual Wibeee Max ...