21
Instruction Manual
RGU-10A
Access the lock menu by pressing the key
. (See
Note:
If no key is pressed for 1 minute, the device goes to Channel 1's
display screen.
Screen with information on the device version. Press the key
to see the version of the
RGU-10A
.
5�2 - TRIP DISPLAY SCREENS
If a trip has been generated, the main display screen will be shown in red, the
Alarm
LED will be lit in
red and the last cycle current that tripped the relay will be displayed.
Trip current
(mA)
Trip delay
Leakage current that tripped the relay
(mA)
If a trip was been generated using the
TRIP/RESET
input, it shows:
Trip current
(mA)
Trip delay
The text EXT, indicating that the trip was through the TRIP/RE-
SET input�
Pressing the key
R
for > 3s or doing an external reset via the
TRIP/RESET
input returns the relay
to its initial status and the main screen display is shown in white.
5�3 - TEST SCREEN
A test can be done to verify the proper functioning of the relay.
To do this, press the key
T
for > 3s while the main display screen is shown.
If the relay has been tripped correctly, the screen in
is displayed. And the
Alarm
LED is lit in
red.
Содержание RGU-10A
Страница 1: ...INSTRUCTION MANUAL Protection and monitoring relay RGU 10A M359B01 03 22A...
Страница 2: ...2 RGU 10A Instruction Manual...
Страница 38: ...38 RGU 10A Instruction Manual 11 EU DECLARATION OF CONFORMITY...
Страница 39: ...39 Instruction Manual RGU 10A...
Страница 40: ...40 RGU 10A Instruction Manual...
Страница 43: ...43 Instruction Manual RGU 10A...