Circutor RGU-10A Скачать руководство пользователя страница 12

12

RGU-10A

Instruction Manual

Conductor routing must be neat, centred and separated from the transformer’s inner opening, 

Figure 11

.

L1

L3

L2

N

Figure 11:Correct distribution of conductors�

The inadequate arrangement of the conductors, as shown in 

Figure 12

, as well as not 

following the recommendations indicated in 

Figure 13

,

 can cause the transformer 

to lose its measurement efficiency and residual current protection. Unexpected 

disconnections may occur in the installation if the 

WGC

 is associated to a differential 

relay that actuates the circuit breaker.

L1

N

L3

L2

N

L2

L1

L3

Figure 12:Incorrect distribution of conductors�

The elbows of the conductors passing through the 

WGC 

must be avoided, both at inlet (before feed-

through) and outlet (after feed-through),

Figure 13

.

L

L

L>

Figure 13:Avoid elbows in conductors�

Содержание RGU-10A

Страница 1: ...INSTRUCTION MANUAL Protection and monitoring relay RGU 10A M359B01 03 22A...

Страница 2: ...2 RGU 10A Instruction Manual...

Страница 3: ...o connecting the device Follow all installation and maintenance in structions throughout the device s working life Pay special attention to the installation standards of the National Electrical Code R...

Страница 4: ...AGE COIL 14 4 OPERATION 15 4 1 PRINCIPLE OF OPERATION 15 4 2 LED INDICATORS 15 4 3 DISPLAY 16 4 4 KEYBOARD FUNCTIONS 17 4 5 RELAY 18 4 6 DIGITAL INPUT 18 5 DISPLAY 20 5 1 DISPLAY SCREENS 20 5 2 TRIP D...

Страница 5: ...purposes only and may differ from the original device SYMBOLS Table 2 Symbols Symbol Description In accordance with the relevant European directive Device covered by European Directive 2012 19 EC At...

Страница 6: ...com pany and or CIRCUTOR s after sales service 2 PRODUCT DESCRIPTION The RGU 10A is a type A ultraimmunised earth leakage protection and monitoring relay that is com patible with the earth leakage tr...

Страница 7: ...tage or current values The manufacturer of the device is not responsible for any damage resulting from failure by the user or installer to heed the warnings and or recommendations set out in this manu...

Страница 8: ...breaker or equiv alent device to disconnect the device from the mains supply 3 3 PANEL MOUNTING ACCESSORY 72 x 72 mm Note The 72 x 72 mm panel mounting accessory is sold separately CIRCUTOR has a pan...

Страница 9: ...Terminals of the RGU 10A Upper Lower Table 4 List of RGU 10A terminals Device terminals A1 A1 Power supply 5 R2 Pre alarm relay NC A2 A2 Power supply 6 C2 Pre alarm relay Common 1 R1 Trip relay NO 7...

Страница 10: ...or window of the transformer 3 5 1 PANEL INSTALLATION For panel installation 4 clamping clips are provided with the transformer see Figure 5 Figure 5 Clamping clip The clamping clips must be installe...

Страница 11: ...ors are defined as the phases L1 L2 and L3 and neutral Never the protection cable PE or Earth Figure 9 PE N L1 L3 L2 Figure 9 Distribution of the conductors Routing the Earth cable PE and the rest of...

Страница 12: ...ted in Figure 13 can cause the transformer to lose its measurement efficiency and residual current protection Unexpected disconnections may occur in the installation if the WGC is associated to a diff...

Страница 13: ...6 CONNECTION DIAGRAMS 3 6 1 CONNECTION WITH EMISSION COIL Alimentaci n Auxiliar Power Supply TRIP RESET 6 2 3 4 5 1 U CARGA LOAD L1 L2 L3 N 1S2 1S1 1S2 1S1 WGC R2 R1 7 8 19 20 A2 A1 Figure 14 Connect...

Страница 14: ...Manual 3 6 2 CONNECTION WITH UNDERVOLTAGE COIL Alimentaci n Auxiliar Power Supply TRIP RESET U CARGA LOAD L1 L2 L3 N 1S2 1S1 1S2 1S1 WGC 7 8 19 20 A2 A1 6 2 3 4 5 1 R2 R1 Figure 15 Connection diagram...

Страница 15: ...ual current protection of the installation such as sensitivity delay and instantaneous leakage current are shown on the display In normal operating conditions the display is shown in White Blue if in...

Страница 16: ...re 17 RGU 10A display areas The data area which displays all the values measured by the device as well as the sensitivity or delay settings The unit and device status area which displays the different...

Страница 17: ...w The pre alarm has been activated Red A relay has tripped due to leakage current see 5 2 TRIP DISPLAY SCREENS An Individual test has been carried out see 5 3 TEST SCREEN An error has been detected se...

Страница 18: ...Figure 18 RGU 10A relay 4 6 DIGITAL INPUT The device has a digital input TRIP RESET Figure 19 to do an external trip or reset If this input is activated the relay is tripped See 5 2 TRIP DISPLAY SCREE...

Страница 19: ...If the R1 trip relay is tripped when a voltage is applied to the TRIP RESET digital input the RGU 10 indicates that there has been a trip and when the voltage is no longer applied to the digital input...

Страница 20: ...e main display screen shows the leakage current and the trip current and delay values Figure 23 Instantaneous leakage current Trip current Trip delay Figure 23 Main display screen Use the keys and to...

Страница 21: ...d Trip current mA Trip delay Leakage current that tripped the relay mA If a trip was been generated using the TRIP RESET input it shows Trip current mA Trip delay The text EXT indicating that the trip...

Страница 22: ...to the channel display screen Figure 25 Test Error 5 4 LOCK To enter the lock menu we must display the Lock screen and press the key Figure 26 Lock menu The lock configuration screen is shown If the...

Страница 23: ...the lock on the device is deactivated Hold down the key for 3s to validate the data and exit the programming Note If no key is pressed for 1 minute the device will lock automatically 5 5 ERROR SCREEN...

Страница 24: ...he symbol See 5 4 LOCK to modify the lock option Note In ANNEX A DIRECT SETTINGS we can see the configuration tree 6 1 TRIP CURRENT The relay s trip current is configured in this screen Use keys and t...

Страница 25: ...he delay of the relay trip or the type of trip curve Use keys and to skip through the different options Configuration values Table 10 Configuration values Delay and relay curve Delay and relay curve P...

Страница 26: ...ration on the RGU 10A is organised into 2 menus Figure 28 3s Pre alarm Relay Trip Relay 3s 3s Figure 28 Configuration menu Note In ANNEX B CONFIGURATION MENU we can see the configuration tree 7 1 PRE...

Страница 27: ...ent at which the pre alarm will be activated according to the of the relay s trip current Alarma Press the key to enter edit mode the programming value flashes Use the keys and to modify the value Con...

Страница 28: ...ss once the key 7 1 3 PRE ALARM OPERATION This screen is used to configure the operation of the pre alarm Press the key to enter edit mode the programming value flashes Use the keys and to skip throug...

Страница 29: ...polarity the polarity of the contacts is reversed with respect to the standard polarity NO the pre alarm relay works with standard polarity Hold down the key for 3s to validate the data and exit edit...

Страница 30: ...old down the key for 3s to validate the data and exit edit mode To skip to the next programming point press once the key 7 2 2 TRIP CURRENT LIMIT In this section the trip current limit is set which ca...

Страница 31: ...t Icw 32 kA 1s Conditional short circuit differential current I c 1500 A Uimp of the voltage source 4 kV CAT III Relay outputs Quantity 2 Maximum voltage open contacts 230 V 15 Maximum current 6 A Max...

Страница 32: ...ble from WGC to RGU 10A Maximum length 10 m Dimensions Figure 33 mm Weight 186 g Enclosure Self extinguishing V0 plastic Standards Low voltage switchgear and control gear Part 2 Circuit breakers Annex...

Страница 33: ...000 A 1000 mA WGC 180 600 800 A 3600 A 1000 mA WGC 220x105 1000 1250 A 7500 A 3000 mA WGC 350x150 1500 2000 A 10000 A 3000 mA WGC 500x200 2500 4000 A 10000 A 3000 mA 2 Imax Maximum transient current p...

Страница 34: ...DIN rail attachment With accessory PA TC WG Enclosure Polycarbonate V0 self extinguishing Standards Instrument transformers Part 1 General requirements IEC 61869 1 Instrument transformers Part 2 Addi...

Страница 35: ...55 WGC 80 WGC 110 WGC 140 and WGC 180 dimensions in mm Table 18 WGC 55 WGC 80 WGC 110 WGC 140 and WGC 180 dimensions Dimensions and Weight Model A B D D Weight WGC 25 25 mm 60 5 mm 64 mm 80 g WGC 35 3...

Страница 36: ...s in mm Table 19 WGC 220x105 WGC 350x150 and WGC 500x200 dimensions Dimensions in mm and Weight Model A B D D E F G H I J K Weight WGC 220x105 200 7 35 195 54 2 314 275 220 105 102 105 3 740 kg WGC 35...

Страница 37: ...erived from a possible failure improper installation or improper usage of the unit Consequently this guarantee does not apply to failures occurring in the following cases Overvoltages and or electrica...

Страница 38: ...38 RGU 10A Instruction Manual 11 EU DECLARATION OF CONFORMITY...

Страница 39: ...39 Instruction Manual RGU 10A...

Страница 40: ...40 RGU 10A Instruction Manual...

Страница 41: ...10A ANNEX A DIRECT SETTINGS Trip current Delay and relay curve N S 0 4 1 0 0 2 0 3 0 5 0 8 3s mA 30mA mA mA mA mA A A A A A A A A1 A1 A1 A1 Possible values if the trip current limit has been set 7 2 2...

Страница 42: ...nstruction Manual ANNEX B SETUP MENU Pre alarm current Pre alarm operation Delay of the pre alarm relay Polarity Polarity Trip current limit T1 MANU AUTO D YES no 3s 3s 3s 3s 3s 3s 3s 3s 3s 5s 3s 1s Y...

Страница 43: ...43 Instruction Manual RGU 10A...

Страница 44: ...CIRCUTOR S A U Vial Sant Jordi s n 08232 Viladecavalls Barcelona Tel 34 93 745 29 00 Fax 34 93 745 29 14 www circutor com central circutor com...

Отзывы: