37
Instruction Manual
RGU-10, RGU-10C
6.2.- MODBUS PROTOCOL
In the Modbus protocol, the
RGU-10C
uses the RTU (Remote Terminal Unit) mode.
The Modbus functions implemented in the device are as follows:
Function 0x04
: Reading integer registers.
Function 0x10
: Writing multiple registers.
6�2�1� READ EXAMPLE: Function 0x04�
Query:
Address
Function
Initial
Register
No� of
registers
CRC
0A
04
0000
000A
7176
Address: 0A
, Peripheral number: 10 in decimal.
Function: 04
, Read function.
Initial Register:0000
, register from which to start reading.
No� of Registers: 000A
, number of registers to be read: 10 in decimal.
CRC: 7176
, CRC character.
Response:
Address Function
No� of
Bytes
Registers
CRC
nº 1
nº 2
nº 3
nº 4
nº 5
nº 6
nº 7
nº 8
nº 9
nº 10
0A
04
14
000A 0002 0000 0032 0000 0001 0000 0001 0014 0000 7EC9
Address: 0A
, Responding peripheral number: 10 in decimal.
Function: 04
, Read function.
No� of bytes: 14
, No. of bytes received: 20 in decimal.
Registers: 000A,
Address 0000h: Peripheral number : 10
0002,
Address 00001h: Baud rate : 2 = 9600 bds
0000,
Address 00002h: Type of parity : 0 = None
0032,
Address 00003h: Operating frequency : 50 Hz
0000,
Address 00004h: Trip current : 0 = 30 mA
0001,
Address 00005h: Time for trip delay : 1 = INS
0000,
Address 00006h: Relay output trip polarity : 0 = Standard
0001,
Address 00007h: % I∆n trip by pre-alarm. : 1 = 50%
0014,
Address 00008h: Time for pre-alarm delay: 1 = 20ms
0000,
Address 00009h: Pre-alarm output relay polarity : 0 = Standard
CRC: 7EC9
, CRC character.
Note :
Each Modbus frame has a maximum limit of 26 registers.
Содержание RGU-10
Страница 1: ...INSTRUCTION MANUAL Electronic earth leakage protection relay RGU 10 RGU 10C M98203201 03 18A ...
Страница 2: ...2 RGU 10 RGU 10C Instruction Manual ...
Страница 43: ...43 Instruction Manual RGU 10 RGU 10C 10 CE CERTIFICATE ...
Страница 44: ...44 RGU 10 RGU 10C Instruction Manual ...
Страница 45: ...45 Instruction Manual RGU 10 RGU 10C ...