29
Instruction Manual
RGU-10, RGU-10C
or SEL
.
5�1�3�-POSITIVE SECURITY SETTING OF THE MAIN RELAY
“
Std”
, contacts are on standby, terminals 14 - 15 (NC) and 13 - 15 (NO).
“
+
”, contacts change status on powering the device, the
+
sign is displayed. Terminals 14 -15
(NO) and 13 -15 (NC).
Figure 24: Positive security setting�
5�1�4�- SETTING THE PRE-ALARM RELAY
The
PROG/PAG
key control the pre-alarm relay and main relay settings using
SETUP
.
If the button is pressed for a short time the pre-alarm setting is entered. “
Alarm
” appears on the
display. Also the pre-alarm threshold appears as a % of the sensitivity setting and the pre-alarm
delay. To exit press
PROG
.
Figure 25: Setting the pre-alarm relay�
5�1�4�1�- Setting of the pre-alarm current
This is in terms of the program value in the main relay. Pressing
Id
enters to change the value.
Relative values are shown as a % of the preset trip current. Pressing
Id
changes the values:
OFF, 50, 60, 70, 80 a
nd
MAIN�
Where:
OFF:
pre-alarm disabled
MAIN:
the pre-alarm continues to trip the main channel.
Figure 26: Setting of the pre-alarm current�