background image

32

RGU-10 MT

Instruction Manual

 

8.- RS-485 COMMUNICATIONS

       

 8�1�- MODBUS CONNECTION

The RS-485 connection must be wired using twisted pair cable with a mesh shield (minimum 3 wires), 

with a maximum distance of 1200 meters between the 

RGU-10C MT

 and the master unit. A maximum 

of 32 slave devices can be connected to this bus.

       

 8�2�- MODBUS PROTOCOL

The 

RGU-10C MT

 model communicates using the MODBUS RTU© protocol (query/reply polling).

Within the Modbus protocol, RTU (Remote Terminal Unit) mode is used; each 8-bit byte in a message 

contains two 4-bit hexadecimal characters. The format for each byte in RTU mode

Code: 

   

           8 binary bits, hexadecimal  0-9, A-F

 

 

 

2 hexadecimal characters contained in each 8-bit field of the message.

Bits per byte:  

 

8 data bits

Check-Error:

             CRC (Cyclical Redundancy Check) type

Modbus functions used:

Function 0x03: 

Read

 

Function 0x06: 

Write

8�2�1�- READING EXAMPLE

Query:

Peripheral 

Function

Initial 

register

Nº of registers 

CRC

0A

03

0000

000A

7176

Peripheral number: 

 

0A, 10 in decimal

Read function:

 

03

Register where you want the reading to start: 

 00 00

Number of registers to read: 

 00 0A , 10 in decimal

CRC character: 

 71 76

Response:

Peripheral 

Function

Nº of 

bytes

Reading

CRC

0A

03

14

00 0A 00 02 00 00 00 32 00 00 00 

01 00 00 00 01 00 14 00 00

7EC9

Peripheral number: 

 

0A, 10 in decimal

Read function:

 

03

Number of bytes received: 

 14, 20 in decimal

Registers: 

 

00 0A: Address 0000: Peripheral number (10)

 00 02:

 

Address

 

0001: Communication baud rate (2- 9600 bauds)

 00 00: Address 0001: Parity type (0 - None)

Содержание RGU-10 MT

Страница 1: ...INSTRUCTION MANUAL Electronic earth leakage protection relay RGU 10 MT Serie M98228501 03 21A...

Страница 2: ...2 RGU 10 MT Instruction Manual...

Страница 3: ...lly prior to connecting the unit Follow all installation and maintenance in structions throughout the unit s working life Pay special attention to the installation standards of the National Electrical...

Страница 4: ...9 4 6 OPERATION 20 4 7 TROUBLESHOOTING OR REASONS FOR TRIPPING 22 4 7 1 POOR TOROID CONNECTION ALARM 22 4 7 2 TRIP ON DIFFERENTIAL FAILURE 22 4 7 3 TRIP ON CIRCUIT BREAKER FAILURE 23 4 7 4 REMOTE TRIP...

Страница 5: ...e original device SYMBOLS Table 2 Symbols Symbol Description In compliance with the relevant European directive In accordance with the CMiM directive In accordance with the UKCA directive UK Conformit...

Страница 6: ...d provide earth leakage overcurrent protection and the interlock function to indicate that the maximum number of reclosings has been reached Allows the setting and adjustment of all parameters require...

Страница 7: ...tandard IEC 61008 1 IEC755 3 modules DIN rail In a panel using front accessory Displaying instant leakage values Backlit LCD display RGU 10C MT RS 485 communication Modbus RTU The measurement of the e...

Страница 8: ...peration of the device to measuring the specified current or voltage values The manufacturer of the device shall not be held responsible for any damage resulting from the user or installation company...

Страница 9: ...sted cable should be used if connecting the earth leakage transformer over long distances 3 2 1 INSTALLATION OF DEVICE IN PANEL A 72x72 mm front adapter accessory is used to install the device on a pa...

Страница 10: ...Power supply State of the circuit breaker 4 Transformer current input 1S1 12 State of the circuit breaker 5 Trip Contact Coil Common 13 Motor output contact OFF 6 Trip Contact Coil NO 14 Motor output...

Страница 11: ...L C1 C2 O I 12 11 1S1 1S2 Type WG External ON OFF Disparo por BOBINA Trip by COIL 7 8 1 2 4 5 6 10 11 13 14 15 Reset Test RGU 10 MT 12 3 9 MT C 6 2 64 TRIP SEC T St Bobina de emisi n Pt Bobina de m n...

Страница 12: ...er which is the MT C 62 64 mo torized circuit breaker CARGA LOAD N L1 L2 L3 M N L O I 12 11 Ty pe W G External ON OFF Disparo por MOTOR OFF Trip by OFF MOTOR 7 8 1 2 4 5 6 10 11 13 14 15 Reset Test RG...

Страница 13: ...OAD N L1 L2 L3 M U N L C1 C2 O I 16 17 S1 S2 Type External ON OFF 7 8 1 2 4 5 6 10 11 13 14 15 Reset Test RGU 10 MT 12 3 9 TRIP SEC T St Bobina de emisi n Pt Bobina de m nima AJUSTE POR ON OFF externo...

Страница 14: ...is the RECmax MP C D2 4 motorized circuit breaker CARGA LOAD N L1 L2 L3 M N L O I 16 17 Ty pe External ON OFF 7 8 1 2 4 5 6 10 11 13 14 15 Reset Test RGU 10 MT 12 3 9 S1 S2 RECmax MP C D2 4 Alimentaci...

Страница 15: ...TION WITHOUT COIL WITH MT TSD CIRCUIT BREAKER The device is connected to the power supply before the circuit breaker which is the MT TSD motorized circuit breaker Figure 9 RGU 10 MT Connection without...

Страница 16: ...current leakage Display Backlit LCD display Small size 3 m dule DIN rail Panel Adapter accessory Output Relays Programming of parameters ASSOCIATED BREAKING DEVICE Earth leakage device with trip coil...

Страница 17: ...M key SAFETY key DELAY key Figure 11 Description LEDs and button 4 3 LEDs INDICATORS The device has 2 indicators LEDs Figure 11 Table 4 LEDs description ON LED ON LED State Description Off The device...

Страница 18: ...g the expanded scale in the settings adds 5 10 and 30 A to the list of values above DELAY td It allows to choose between the values of 20 100 200 300 400 500 750 ms and 1 s Specifying the expanded sca...

Страница 19: ...device trips through any event the screen s background changes to red and the reason for the trip is displayed Figure 12 Display RGU 10 MT Display messages by device trip Table 6 Table 6 Display mess...

Страница 20: ...mbols while the device is being pro grammed and set Figure 14 Trip sensitivity Instant current leakage Active reconnection Contact polarity Trip delay Configuration setting Communications configuratio...

Страница 21: ...device uses 4 screens 2 fixed and 2 floating To switch between them short press the PROG key Fixed screens These screens display the delay the programmed nominal current the current leakage current a...

Страница 22: ...r Also the ERRt error message will permanently appear on the RGU 10 MT display A short circuit in the transformer secondary will also be detected as an error When this error is detected the correct co...

Страница 23: ...It is not possible to manually reset or reset using communications Figure 19 Remote trip When it is remotely reset input terminals 1 2 the device is reconnected with the display backlit in green LED O...

Страница 24: ...ting in the main figures Figure 21 Setting the sensitivity trip Possible setting values are 30 mA 100 mA 300 mA 500 mA 1 A 3 A 5 A 10 A and 30 A Only one scale is displayed To change the scale see Sec...

Страница 25: ...IVE SAFETY SETTING OF THE INTERLOCK RELAY Std contacts are on standby terminals 7 NO 8 Common and 9 NC contacts change status on powering the device the sign is displayed Terminals 7 NC 8 Com mon and...

Страница 26: ...26 RGU 10 MT Instruction Manual 6 CONFIGURATION ADJUSTMENTS USING SETUP MENU To access the setup menu long press the PROG key PROG will be shown on the display Figure 24 Setup menu...

Страница 27: ...communications menu the menu s home screen is displayed Figure 25 Figure 25 Home screen of the communications menu Press the PROG key to access the configuration parameters 6 1 1 PERIPHERAL NUMBER To...

Страница 28: ...sing the PROG key 6 2 MEASUREMENT CONFIGURATION 6 2 1 WORKING FREQUENCY The display shows FREC To change the value press the PROG key The currently set frequency value is shown at the top left of the...

Страница 29: ...change the circuit breaker press the td key repeatedly Programming values Mb coil trip or Ma magnetothermic trip When the desired value is shown on the screen validate the number by pressing the PROG...

Страница 30: ...play shows SEC T To change the value press the PROG key To modify the status of the contactors on the coil press the td key repeatedly Programming values St standard or PS positive signal When the des...

Страница 31: ...TOTHERMIC While the screens of differential and magnetothermic are displayed floating screens it is possible to view or modify The number of partial and total reclosings Assign the maximum number of r...

Страница 32: ...cimal characters contained in each 8 bit field of the message Bits per byte 8 data bits Check Error CRC Cyclical Redundancy Check type Modbus functions used Function 0x03 Read Function 0x06 Write 8 2...

Страница 33: ...01 00 03 00 00 00 3C 00 00 FF 64 Peripheral number 01 Write function 10 write multiple registers Register where you want the write to start 00 00 Number of registers to write 00 05 N of bytes to write...

Страница 34: ...4 0 2 5 0 3 6 0 4 7 0 5 8 0 75 9 1 A 3 B 5 C 10 s Latch Relay Contacts Polarity 03 06 0009 0 Standard 1 Positive Total number of reconnections 03 06 0008 0 9999 Device version 03 000D 0 100 Status of...

Страница 35: ...tage 230 V Rated current 6 A Instantaneous maximum current 10 A Rated load in AC 2500 VA Contacts protected by varistor Maximum voltage 275 V Mechanical useful life 10 x 106 operations Electrical usef...

Страница 36: ...Sides and back cover Mechanical features Dimensions Figure 27 Weight 168 g Enclosure V0 Polycarbonate plastic Fixing DIN Rail Panel by accessory Terminals 7 mm 0 127 2 082 mm2 0 5 0 6 Nm Bar 0 4x2 5x8...

Страница 37: ...from a possible failure improper installation or improper usage of the unit Consequently this guarantee does not apply to failures occurring in the following cases Overvoltages and or electrical dist...

Страница 38: ...38 RGU 10 MT Instruction Manual 12 CE CERTIFICATE...

Страница 39: ...39 Instruction Manual RGU 10 MT...

Страница 40: ...40 RGU 10 MT Instruction Manual...

Страница 41: ...41 Instruction Manual RGU 10 MT...

Страница 42: ...CIRCUTOR SA Vial Sant Jordi s n 08232 Viladecavalls Barcelona Tel 34 93 745 29 00 Fax 34 93 745 29 14 www circutor es central circutor com...

Отзывы: